3.1 Variable Area (setup range) List
E5AN/EN/CN/GN
3--7
Variable
type
Address
Item
Set (monitor) Value
Level
C3
0029
MV upper limit
Standard: MV lower limit +0.1 to 000041A
(MV lower limit +0.1 to 105.0)
Advanced func-
tion setting
Heating and cooling: 00000000 to 0000041A
(0.0 to 105.0)
g
C3
002A
MV lower limit
Standard: FFFFFFCE to MV upper limit -0.1
(-5.0 to MV upper limit -0.1)
Heating and cooling: FFFFFBE6 to 00000000
(-105.0 to 0.0)
C3
002B
Input digital filter
00000000 to 0000270F (0.0 to 999.9)
C3
002C
Additional PV dis-
play
00000000(0):
OFF
00000001(1):
ON
C3
002D
MV display
00000000(0):
OFF (display of manipulated variable
OFF)
00000001(1):
ON (display of manipulated variable
ON)
C3
002E
Automatic return of
display mode
00000000(0):
OFF
00000001 to 00000063 (1 to 99)
C3
002F
Alarm 1 latch
00000000(0):
OFF
00000001(1):
ON
C3
0030
Alarm 2 latch
00000000(0):
OFF
00000001(1):
ON
C3
0031
Alarm 3 latch
00000000(0):
OFF
00000001(1):
ON
C3
0032
Protect level move
time
00000001 to 0000001E (1 to 30)
C3
0033
Input error output
00000000(0):
OFF
00000001(1):
ON
C3
0034
Cold junction com-
pensation method
00000000(0):
OFF
00000001(1):
ON
C3
0035
MB command logic
switching*
1
00000000(0):
OFF
00000001(1):
ON
C3
0036
PV color change*
2
00000001(1):
Red
00000002(2):
Green
00000003(3):
Red
®
Green ALM1 lit : Green
00000004(4):
Green
®
Red ALM1 lit : Red
00000005(5):
Red
®
Green
®
Red
Within PV stable band : Green
Outside the stable band : Red
C3
0037
PV stable band*
2
00000001 to 0000270F (0.1 to 999.9)
*
1
The logic is switched only in MB command (Sysway).
The logic of CompoWay/F operation instruction code 00 (communications writing) is not influenced.
*
2
Applies to the E5CN only.