3.1 Variable Area (setup range) List
E5AN/EN/CN/GN
3--5
Variable
type
Address
Item
Set (monitor) Value
Level
C3
0004
_
C/
_
F selection
00000000(0):
_
C
00000001(1):
_
F
Initial setting
C3
0005
SP upper limit
Temperature:
SP lower limit +1 to Input range upper limit
Analog: SP lower limit +1 to scaling upper limit
C3
0006
SP lower limit
Temperature:
Input range lower limit to SP upper limit -1
Analog: Scaling lower limit to SP upper limit -1
C3
0007
PID/ ON/OFF
00000000(0):
ON/OFF
00000001(1):
2-PID
C3
0008
Standard/Heating and
cooling
00000000(0):
Standard
00000001(1):
Heating and cooling
C3
0009
ST
00000000(0):
OFF
00000001(1):
ON
C3
000A
Control period (OUT1)
00000001 to 00000063 (1 to 99)
C3
000B
Control period (OUT2)
00000001 to 00000063 (1 to 99)
C3
000C
Direct/reverse opera-
tion
00000000(0):
Reverse operation
00000001(1):
Direct operation
C3
000D
Alarm 1 type
00000000(0):
Alarm function OFF
00000001(1):
Upper- and lower-limit alarm
00000002(2):
Upper-limit alarm
00000003(3):
Lower-limit alarm
00000004(4):
Upper- and lower-limit range alarm
00000005(5):
Upper- and lower-limit alarm with
standby sequence
00000006(6):
Upper-limit alarm with standby
sequence
00000007(7):
Lower-limit alarm with standby
sequence
00000008(8):
Absolute-value upper-limit alarm
00000009(9):
Absolute-value lower-limit alarm
0000000A(10): Absolute-value upper-limit alarm
with standby sequence
0000000B(11): Absolute-value lower-limit alarm
with standby sequence
C3
000E
Alarm 2 type
Same as alarm 1 type
C3
000F
Alarm 3 type *
Same as alarm 1 type
* The alarm function can be also be utilized on units without alarm output terminals. In this case, confirm alarm occurrences via the
status data.