3.1 Variable Area (setup range) List
E5AN/EN/CN/GN
3--3
Variable
type
Address
Item
Set (monitor) Value
Level
C1
0000
Operation/adjustment
protection
00000000(0):
No restrictions in operation and
adjustment levels
00000001(1):
Move to adjustment level restric-
ted
00000002(2):
Display and change of only “PV”
and “PV/SP” parameters enabled
00000003(3):
Display of only “PV” and “PV/SP”
parameters enabled
Protect
C1
0001
Initial setting/commu-
nications protection
00000000(0):
Move to initial setting/commu-
nications setting level enabled
(move to advanced function set-
ting level displayed)
00000001(1):
Move to initial setting/commu-
nications setting level enabled
(move to advanced function set-
ting level not displayed)
00000002(2):
Move to initial setting/commu-
nications setting level restricted
C1
0002
Setup change protection 00000000(0):
OFF (changing of setup on con-
troller display enabled)
00000001(1):
ON (changing of setup on con-
troller display disabled)
C1
0003
Set point
SP lower limit to SP upper limit
Operation
C1
0004
Alarm value 1
FFFFF831 to 0000270F (-1999 to 9999)
C1
0005
Upper-limit alarm 1
FFFFF831 to 0000270F (-1999 to 9999)
C1
0006
Lower-limit alarm 1
FFFFF831 to 0000270F (-1999 to 9999)
C1
0007
Alarm value 2
FFFFF831 to 0000270F (-1999 to 9999)
C1
0008
Upper-limit alarm 2
FFFFF831 to 0000270F (-1999 to 9999)
C1
0008
Lower-limit alarm 2
FFFFF831 to 0000270F (-1999 to 9999)
C1
000A
Alarm value 3 *
FFFFF831 to 0000270F (-1999 to 9999)
C1
000B
Upper-limit alarm 3 *
FFFFF831 to 0000270F (-1999 to 9999)
C1
000C
Lower-limit alarm 3 *
FFFFF831 to 0000270F (-1999 to 9999)
C1
000D
Heater burnout detection 00000000 to 000001F4 (0.0 to 50.0)
Adjustment
C1
000E
Set point 0
SP lower limit to SP upper limit
C1
000F
Set point 1
SP lower limit to SP upper limit
C1
0010
Set point 2
SP lower limit to SP upper limit
C1
0011
Set point 3
SP lower limit to SP upper limit
C1
0012
Temperature input shift
FFFFF831 to 0000270F (-199.9 to 999.9)
C1
0013
Upper-limit temperature
input shift value
FFFFF831 to 0000270F (-199.9 to 999.9)
C1
0014
Lower-limit temperature
input shift value
FFFFF831 to 0000270F (-199.9 to 999.9)
C1
0015
Proportional band
00000001 to 0000270F (0.1 to 999.9)
C1
0016
Integral time
00000000 to 00000F9F (0 to 3999)
C1
0017
Derivative time
00000000 to 00000F9F (0 to 3999)
C1
0018
Cooling coefficient
00000001 to 0000270F (0.01 to 99.99)
* Only displayed on the E5EN/AN-
V
3
VVV
.
The alarm function can be also be utilized on units without alarm output terminals. In this case, confirm alarm occurrences via the
status data.