CHAPTER 3 COMMUNICATIONS DATA
E5AN/EN/CN/GN
3--6
Variable
type
Address
Item
Set (monitor) Value
Level
C3
0010
Communications unit
No. *
1
00000000 to 00000063 (0 to 99)
Communica-
tions setting
C3
0011
Baud rate *
1
00000000(0): 1.2
00000001(1): 2.4
00000002(2): 4.8
00000003(3): 9.6
00000004(4): 19.2
g
C3
0012
Communications data
length *
1
00000007(7): 7
00000008(8): 8
C3
0013
Communications stop
bit *
1
00000001(1): 1
00000002(2): 2
C3
0014
Communications parity 00000000(0): None
00000001(1): Even
00000002(2): Odd
C3
001A
Multi-SP
00000000(0): OFF
00000001(1): ON
Advanced func-
tion setting
C3
001B
Spare
g
C3
001C
SP ramp set value
00000000(0): OFF
00000001 to 0000270F (1 to 9999)
C3
001D
Standby sequence
reset method
00000000(0): Condition A
00000001(1): Condition B
C3
001E
Alarm 1 open in alarm
00000000(0):
Close in alarm
00000001(1):
Open in alarm
C3
001F
Alarm 1 hysteresis
00000001 to 0000270F (0.1 to 999.9)
C3
0020
Alarm 2 open in alarm
00000000(0):
Close in alarm
00000001(1):
Open in alarm
C3
0021
Alarm 2 hysteresis
00000001 to 0000270F (0.1 to 999.9)
C3
0022
Alarm 3 open in alarm* 00000000(0):
Close in alarm
00000001(1):
Open in alarm
C3
0023
Alarm 3 hysteresis
00000001 to 0000270F (0.1 to 999.9)
C3
0024
HBA used
00000000(0):
OFF
00000001(1):
ON
C3
0025
Heater burnout latch
00000000(0):
OFF
00000001(1):
ON
C3
0026
Heater burnout hyster-
esis
00000001 to 00001F4 (0.1 to 50.0)
C3
0027
ST stable range
00000001 to 0000270F (0.1 to 999.9)
C3
0028
a
00000000 to 00000064 (0.00 to 1.00)
*1 Communications parameters are enabled after they have been changed by resetting the controller.
* The alarm function can be also be utilized on units without alarm output terminals. In this case, confirm alarm occurrences via
the status data.