![Omron E5AN User Manual Download Page 29](http://html1.mh-extra.com/html/omron/e5an/e5an_user-manual_742571029.webp)
2.3 Details of Services
E5AN/EN/CN/GN
2--15
At occurrence of error
Response code
Error name
Cause
1001
Command too long
The command is too long.
1002
Command too short
The command is too short.
1100
Parameter error
Instruction code and related informa-
tion are wrong.
2203
Operation error
·
The
“communications
writing”
parameter is set to “OFF” (dis-
abled). However, note that the error
is accepted regardless of the “com-
munications writing” parameter set-
ting (ON/OFF).
·
The command cannot be pro-
cessed. For details, see “(3)
Description of operating instruc-
tions and precautions” below.
·
EEPROM error
(3) Description of operation instructions and precautions
F
Communications writing
Set the “communications writing” parameter to “ON: enabled” or
“OFF: disabled” according to related information. This instruction can
be accepted at both setup areas 0 and 1.
F
Run/Stop
Set control to “run” or “stop” according to related information. This
instruction can be accepted at both setup areas 0 and 1.
F
AT execute/cancel
Set AT (auto-tuning) to “execute” or “cancel” according to related
information. This instruction can be accepted at setup area 0 only. How-
ever, note that an “operation error” is generated in the following
instances:
·
When the “run/stop” parameter is set to “stop”
·
When the instruction is issued in “setup area 1”
·
When the ON/OFF control
F
Write mode
Set either the backup mode or RAM write mode according to related
information. This instruction can be accepted at both setup areas 0 and 1.
F
Multi- -SP
Set four set points beforehand in the adjustment level so that you switch
to a desired set point.