CHAPTER 2 CompoWay/F COMMUNICATIONS PROCEDURES
E5AN/EN/CN/GN
2--8
2.3 Details of Services
This service reads from variable areas.
MRC
SRC
Variable
type
Read start
address
Bit
position
Number of
elements
0 1
0
1
0 0
2
2
2
4
2
4
MRC
SRC
Response
code
Read data
(for number of elements)
0 1
0
1
2
2
4
0 or 8 or 16
Service request PDU
Service response PDU
(1) Variable type and read start address
For details on variable types and read start addresses, see “Chapter 3
Communications Data.”
(2) Bit position
Bit accessing is not supported on the E5AN/EN/CN/GN. Fixed to
“00”.
(3) Number of elements
Number of
elements
Process
0000
Read is not carried out (the service response PDU is not
appended with read data), and processing ends in “normal
completion.”
0001 to 0002
Read is carried out, and processing ends in “normal completion.”
(4) Response code
At normal completion
Response code
Name
Description
0000
Normal completion
No errors were found.
At occurrence of error
Response code
Error name
Cause
1001
Command too long
The command is too long.
1002
Command too short
The command is too short.
1101
Area type error
The variable type is wrong.
1103
Start address out-of-
range error
The read start address is
out of range.
110B
Response too long
The number of elements is
larger than “0002”.
1100
Parameter error
The bit position is other than
“00”.
2203
Operation error
EEPROM error
J
Read from
variable area