E5GC
9
Characteristics
*1.
The indication accuracy of K thermocouples in the
−
200 to 1,300
°
C range, T and N thermocouples at a temperature of
−
100
°
C max., and U
and L thermocouples at any temperature is
±
2
°
C
±
1 digit max. The indication accuracy of B thermocouples at a temperature of 400
°
C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800
°
C is
±
3
°
C max.
The indication accuracy of R and S thermocouples at a temperature of 200
°
C max. is
±
3
°
C
±
1 digit max. The indication accuracy of C/W
thermocouples is (
±
0.3% of PV or
±
3
°
C, whichever is greater)
±
1 digit max.
The indication accuracy of PLII thermocouples is (
±
0.3% of PV or
±
2
°
C, whichever is greater)
±
1 digit max.
*2.
However, the precision between 0 and 4 mA for a 0 to 20 mA output is
±
1% FS max.
*3.
Ambient temperature:
−
10
°
C to 23
°
C to 55
°
C, Voltage range:
−
15% to 10% of rated voltage
*4.
K thermocouple at
−
100
°
C max.:
±
10
°
C max.
*5.
The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*6.
External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the same time.
*7.
Refer to your OMRON website for the most recent information on applicable models.
*8.
Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
Indication accuracy
(at the temperature of 23
°
C)
Thermocouple: (
±
0.3 % of indication value or
±
1
°
C, whichever is greater)
±
1 digit max.
*
1
Platinum resistance thermometer: (
±
0.2 % of indication value or
±
0.8
°
C, whichever is greater)
±
1 digit max.
Analog input:
±
0.2% FS
±
1 digit max.
CT input:
±
5% FS
±
1 digit max.
Simple transfer output accuracy
±
0.3% FS max.
*
2
Influence of temperature
*
3
Thermocouple input (R, S, B, C/W, PL II): (
±
1% of indication value or
±
10
°
C, whichever is greater)
±
1 digit max.
Other thermocouple input: (
±
1% of indication value or
±
4
°
C, whichever is greater)
±
1 digit max.
*
4
Platinum resistance thermometer: (
±
1% of indication value or
±
2
°
C, whichever is greater)
±
1 digit max.
Analog input:
±
1% FS
±
1 digit max.
CT input:
±
5% FS
±
1 digit max.
Influence of voltage
*
3
Influence of EMS.
(at EN 61326-1)
Input sampling period
50 ms
Hysteresis
Temperature input: 0.1 to 999.9
°
C or
°
F (in units of 0.1
°
C or
°
F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
Temperature input: 0.1 to 999.9
°
C or
°
F (in units of 0.1
°
C or
°
F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
*
5
Derivative time (D)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
*
5
Proportional band (P) for cooling
Temperature input: 0.1 to 999.9
°
C or
°
F (in units of 0.1
°
C or
°
F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
*
5
Derivative time (D) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
*
5
Control period
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0% to 100.0% (in units of 0.1%)
Alarm setting range
−
1,999 to 9,999 (decimal point position depends on input type)
Influence of signal source
resistance
Thermocouple: 0.1
°
C/
Ω
max. (100
Ω
max.), Platinum resistance thermometer: 0.1
°
C/
Ω
max. (10
Ω
max.)
Insulation resistance
20 M
Ω
min. (at 500 VDC)
Dielectric strength
100 to 240 VAC: 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
24 VAC/DC: 2,300 VAC, 50/60 Hz for 1 min between terminals of different charge
Vibration
Malfunction
10 to 55 Hz, 20 m/s
2
for 10 min each in X, Y and Z directions
Resistance
10 to 55 Hz, 20 m/s
2
for 2 hr each in X, Y, and Z directions
Shock
Malfunction
100 m/s
2
, 3 times each in X, Y, and Z directions
Resistance
300 m/s
2
, 3 times each in X, Y, and Z directions
Weight
Controller: Approx. 80 g, Mounting Adapter: Approx. 4 g
×
2
Degree of protection
Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool
CX-Thermo version 4.62 or higher
Setup Tool port
E5GC side panel:
An E58-CIFQ2 USB-Serial Conversion Cable is used to connect a USB port on the
computer.
*
6
E5GC bottom panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable
are used together to connect a USB port on the computer.
*
6
Standards
Approved standards
cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark) (Some
models only.)
*
7, EAC
Conformed standards
EN 61010-1 (IEC 61010-1), RCM
EMC
EMI:
EN61326-1
*
8
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1, class A
Noise Terminal Voltage:
EN55011 Group 1, class A
EMS:
EN61326-1
*
8
ESD Immunity:
EN61000-4-2
Electromagnetic Field Immunity:
EN61000-4-3
Burst Noise Immunity:
EN61000-4-4
Conducted Disturbance Immunity:
EN61000-4-6
Surge Immunity:
EN61000-4-5
Voltage Dip/Interrupting Immunity:
EN61000-4-11