![Omron E5 C Series Manual Download Page 126](http://html1.mh-extra.com/html/omron/e5-c-series/e5-c-series_manual_742537126.webp)
E5
@
C/E5
@
C-T
126
E5CC/E5CC-B/E5CC-U/E5CC-T
• E5CC/E5CC-T
There are two models of Terminal Covers that you can use with the
E5CC/E5CC-T.
• E5CC-U
For the Wiring Socket for the E5CC-U, purchase the P2CF-11 or
PG3A-11 separately.
1.
For waterproof mounting, waterproof packing must be installed on
the Digital Temperature Controller. Waterproofing is not possible
when group mounting several Digital Temperature Controllers.
The E5CC-U cannot be waterproofed even if the Waterproof
Packing is inserted.
2.
Insert the E5CC/E5CC-B/E5CC-U/E5CC-T into the mounting hole
in the panel.
3.
Push the adapter from the terminals up to the panel, and
temporarily fasten the E5CC/E5CC-B/E5CC-U/E5CC-T.
4.
Tighten the two fastening screws on the adapter.
Alternately tighten the two screws little by little to maintain a
balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
E5EC/E5EC-B/E5AC/E5EC-T/E5AC-T
1.
For waterproof mounting, waterproof packing must be installed on
the Digital Temperature Controller. Waterproofing is not possible
when group mounting several Digital Temperature Controllers.
2.
Insert the E5EC/E5EC-B/E5AC/E5EC-T/E5AC-T into the
mounting hole in the panel.
3.
Push the adapter from the terminals up to the panel, and
temporarily fasten the E5EC/E5EC-B/E5AC/E5EC-T/E5AC-T.
4.
Tighten the two fastening screws on the adapter.
Alternately tighten the two screws little by little to maintain a
balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
E5DC/E5DC-B
1.
Insert the E5DC/E5DC-B into the mounting hole in the panel.
(Attach the Terminal Unit after you insert the Main Unit.)
2.
Push the Adapter from the Terminal Unit up to the panel, and
temporarily fasten the E5DC/E5DC-B.
3.
Tighten the two fastening screws on the Adapter. Alternately
tighten the two screws little by little to maintain a balance. Tighten
the screws to a torque of 0.29 to 0.39 N·m.
E5DC
Mounting to and Removing from DIN Track
• Mounting a Unit
Pull down the DIN Track hook on the Terminal Unit and catch the
top hook on the DIN Track.
Press the Unit onto the DIN Track until the DIN Track hooks are
locked in place.
• Removing a Unit
Pull down on the DIN Track Hook with a flat-blade screwdriver and
lift up the Unit.
Panel
Water Proof Packing
Terminal Cover
(E53-COV17)
(Sold separately)
Adapter
Terminal Cover
(E53-COV23)
Adapter
Adapter
Panel
Water Proof Packing
Terminal Cover
(E53-COV24)
Terminal Cover
(E53-COV24)
Main Unit
Panel
Terminal Unit
Adapter
1. Pull down the hook.
2. Catch the top hook on
the DIN Track.
4. Make sure that the hooks
are locked in place.
3. Press the Unit onto
the DIN Track.