![Omron E5 C Series Manual Download Page 11](http://html1.mh-extra.com/html/omron/e5-c-series/e5-c-series_manual_742537011.webp)
E5GC
11
External Connections
E5GC
Note: 1.
The application of the terminals depends on the model.
2.
Do not wire the terminals that are shown with a gray background.
3.
When complying with EMC standards, the cable that connects the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
4.
Connect M3 crimped terminals.
5.
Due to UL Listing requirements, use the E54-CT1L or E54-CT3L Current Transformer with the factory wiring (internal wiring).
Use a UL category XOBA or XOBA7 current transformer that is UL Listed for field wiring (external wiring) and not the factory wiring
(internal wiring).
Isolation/Insulation Block Diagrams
Note:
Auxiliary outputs 1 to 2 are not insulated.
E5GC-
@@@@@
M -
@@@
(1) (2)(3)(4)(5)
(6)
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Load: 500
Ω
max.
Voltage output (for driving SSR)
12 VDC, 21 mA
Relay output
250 VAC, 2 A
(resistive load)
250 VAC, 2 A
(resistive load)
Relay outputs
Control Outputs
Auxiliary outputs 1, 2
↑
Terminal type
The E5GC is set for a K-type thermocouple (input type = 5) by
default. An input error (
s.err
) wil occur if the input type setting
does not agree with the temperature sensor. Check the input type.
CT
7
8
9
EV2
EV1
024
Event inputs 1 and 2
7
8
9
015
Communications
(RS-485)
RS-485
B(+)
A(
−
)
7
8
9
EV1
016
Event input 1
7
8
9
023
CT input
1
2
100 to 240 VAC
1
2
24 VAC/DC
(no polarity)
3
4
RX
Relay output
R
Q
C
3
4
QX
Voltage output (for driving SSR)
3
4
CX
Linear current output
10 11 12
V
V
+
+
−
+
−
+
−
+
−
−
10 11 12
mA
I
10 11 12
TC
10 11 12
Pt
B
A
B
7
8
9
10
11 12
1
2
3
4
5
6
(6) Options
(3) Input Power Supply
(1) Control Outputs
9
5
6
Auxiliary
output 1
Auxiliary
output 2
(2) Auxiliary Outputs
5
6
Auxiliary
output 1
Auxiliary
output 1
Auxiliary outputs 1, 2
(5) Sensor (Temperature/Analog) Input
(
−
)
(
−
)
Use no-voltage inputs for the event inputs.
The polarity for non-contact inputs is given in parentheses.
Sensor input and CT input
Communications and event inputs
Voltage output (for driving SSR) and linear current output
Relay output
Auxiliary outputs 1 and 2
: Reinforced insulation
: Functional isolation
Power
supply
Summary of Contents for E5 C Series
Page 17: ...17 MEMO...
Page 39: ...39 MEMO...
Page 77: ...77 MEMO...
Page 95: ...95 MEMO...
Page 113: ...113 MEMO...
Page 136: ...MEMO 136...