1-4 Description of Safety Functions
1-4-2 Safety
Inputs
Test Pulse from Test Output
A test output is used in combination with a safety input. Specify the corresponding test
output terminal to use as the test source. The test output terminal is used as a power
supply to connect an external input device to the safety input terminal.
V
V
0
1
2
3
4
5
6
7
G
G
T0
T1
T0
T1
T0
T1
T0
T1
Example: DST1-ID12S-1
24 V
Here, IN0 and T0 are used in combination,
24 V DC output with test pulse
External contact
Safety input
terminal
A test pulse is output from the test output terminal to diagnose the internal circuit when
the external input contact turns ON. Using this function, short-circuits between input
signal lines and the power supply (positive side), and short-circuits between input signal
lines can be detected.
External contact
T0
IN0
24 V
0 V
24 V
External contact
T1
IN1
Short-circuit between input signal line and
power supply (positive side)
Short-circuit between input signal lines
V
G
1-12
Summary of Contents for DST1 Series
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ...DST1 series Safety I O Terminals Operation Manual Produced April 2005 ...
Page 6: ......
Page 24: ...Section 1 Overview ...
Page 44: ...Section 2 General Procedure ...
Page 50: ...Section 3 Configuration ...
Page 63: ...Section 4 Specifications ...
Page 67: ...Section 5 DST1 series ...
Page 79: ...Section 6 Troubleshooting and Maintenance ...
Page 87: ...Section 7 Wiring Examples ...
Page 97: ...Appendices ...
Page 114: ...Cat No Z904 E1 01 OPERATION MANUAL DST1 series Safety I O Terminals ...