7-2 Examples of Wiring for Each Application
7-2-6
Safety Light Curtain Input
An example of the wiring and configuration when using the DST1-ID12SL-1 is shown
below.
Wiring
V
G
IN0
T0
IN1
T1
E1
T2
G
GND
0V
+2
4
V
F3SN-A
Emitter
Receiver
OS
SD1
OS
SD2
0V
+2
4
V
E1: 24-V DC Power Supply (S8
)
F3SN-A: Safety Light Curtain
Configuration
Parameter
group
Parameter name
Value
0008 Safety Input 0 Channel Mode
Used as safety input
0009 Safety Input 0 Test Source
Not Used
0054 Dual Channel Safety Input 0/1 Mode
Dual Channel Equivalent
Safety Input 0
0055 Dual Channel Safety Input 0/1 Discrepancy Time 100 x 10 ms
0012 Safety Input 1 Channel Mode
Used as safety input
Safety Input 1
0013 Safety Input 1 Test Source
Not Used
Test Output 2
0003 Test Output 2 Mode
Power Supply Output
7-8