7-2 Examples of Wiring for Each Application
7-2-2 Two-Hand
Input
An example of the wiring and configuration when using the DST1-ID12SL-1 is shown
below.
Wiring
V
G
IN0
T0
IN1
T1
E1
S11
IN2
T0
IN3
T1
S12
→
→
GND
E1: 24-V DC Power Supply (S8
)
S11,S12: Two-hand control switches
Configuration
Parameter
Group
Parameter Name
Value
0008 Safety Input 0 Channel Mode
Test pulse from test output
0009 Safety Input 0 Test Source
Test Output 0
0054 Dual Channel Safety Input 0/1 Mode
Dual Channel Complementary
Safety Input 0
0055 Dual Channel Safety Input 0/1 Discrepancy Time 100 x 10 ms
0012 Safety Input 1 Channel Mode
Test pulse from test output
Safety Input 1
0013 Safety Input 1 Test Source
Test Output 0
0016 Safety Input 2 Channel Mode
Test pulse from test output
0017 Safety Input 2 Test Source
Test Output 1
0056 Dual Channel Safety Input 2/3 Mode
Dual Channel Complementary
Safety Input 2
0057 Dual Channel Safety Input 2/3 Discrepancy Time 100 x 10 ms
0020 Safety Input 3 Channel Mode
Test pulse from test output
Safety Input 3
0021 Safety Input 3 Test Source
Test Output 1
Test Output 0
0001 Test Output 0 Mode
Pulse Test Output
Test Output 1
0002 Test Output 1 Mode
Pulse Test Output
7-4
Summary of Contents for DST1 Series
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ...DST1 series Safety I O Terminals Operation Manual Produced April 2005 ...
Page 6: ......
Page 24: ...Section 1 Overview ...
Page 44: ...Section 2 General Procedure ...
Page 50: ...Section 3 Configuration ...
Page 63: ...Section 4 Specifications ...
Page 67: ...Section 5 DST1 series ...
Page 79: ...Section 6 Troubleshooting and Maintenance ...
Page 87: ...Section 7 Wiring Examples ...
Page 97: ...Appendices ...
Page 114: ...Cat No Z904 E1 01 OPERATION MANUAL DST1 series Safety I O Terminals ...