2-5 Node Address
2-5 Node
Address
Set the node address using the two rotary switches on the front panel of the
DST1-series Safety I/O Terminals. The default setting is 63. Set the tens digit of the
node address (decimal) using the left rotary switch and set the ones digit using the right
rotary switch. A value between 00 and 63 can be set.
0
1
2
3
4
5
6
7
8
9
Tens digit of node address
0
1
2
3
4
5
6
7
8
9
Ones digit of node address
If a node address between 64 and 99 is set, the node address can be set from the
Network Configurator.
IMPORTANT
•
The node address must be set while the communications power supply is
turned OFF.
•
Do not change the rotary switches while the power is ON. The DST1-series
Safety I/O Terminals will detect this as a change in the configuration and
will switch to fault state.
•
Use a small flat-blade screwdriver to set the rotary switches, being careful
not to scratch them.
2-6 Configuration
Configure the
DST1-series Safety I/O Terminals using the Network Configurator.
Refer to
Section 3 Configuration
for details on settings. Refer to the
System
Configuration Manual
(Cat.No.Z905) for Network Configurator operating procedures.
2-6
Summary of Contents for DST1 Series
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ...DST1 series Safety I O Terminals Operation Manual Produced April 2005 ...
Page 6: ......
Page 24: ...Section 1 Overview ...
Page 44: ...Section 2 General Procedure ...
Page 50: ...Section 3 Configuration ...
Page 63: ...Section 4 Specifications ...
Page 67: ...Section 5 DST1 series ...
Page 79: ...Section 6 Troubleshooting and Maintenance ...
Page 87: ...Section 7 Wiring Examples ...
Page 97: ...Appendices ...
Page 114: ...Cat No Z904 E1 01 OPERATION MANUAL DST1 series Safety I O Terminals ...