4 Mounting and Wiring
4 - 2
CK3E-series Programmable Multi-Axis Controller Hardware User’s Manual (I610)
4-1
Mounting the Programmable
Multi-Axis Controller
z
Installation in Cabinets or Control Panels
When installing the Programmable Multi-Axis Controller in a cabinet or control panel, consider the
ambient temperature, accessibility for operation and maintenance, noise immunity, as well as the
mounting direction.
z
Temperature Control
The allowable ambient operating temperature range of the Programmable Multi-Axis Controller is 0
to 45°C. When necessary, take the following steps to maintain the appropriate temperature.
• Provide sufficient space for adequate air flow.
• Do not install the Controller directly above equipment that generates a large amount of heat such
as heaters, transformers, or high-capacity resistors.
• If the ambient temperature exceeds 45°C, install a cooling fan or air conditioner.
z
Accessibility for Operation and Maintenance
• To ensure safe access for operation and maintenance, move the Controller as far away as possi-
ble from high-voltage equipment and electrical machinery.
• It will be easy to operate the Controller if it is mounted at a height of 1,000 to 1,600 mm above the
floor.
z
Improving Noise Resistance
• Do not mount the Controller in a control panel containing high-voltage equipment.
• Install the Controller at least 200 mm away from power lines.
• Ground the mounting plate between the Controller and the mounting surface.
4-1-1
Mounting the Programmable Multi-Axis Controller
Control
panel
Fan
CK3E-series
Programmable
Multi-Axis
Controller
Louver
CK3E-series
Programmable
Multi-Axis Controller
Power lines
200 mm min.
200 mm min.