43
Parameter
Default value
Write/Read
data range
Actual data
range
Bank
no.
Loop
no.
Read
Write
Com-
mand
Alarm 1 mode
2
4
Yes
Yes
Yes
No
0 to 9
0000 to
0009
2
Alarm 2 mode
2
5
0009
Yes:
Possible.
No:
Not possible or not required.
Note
1. Only when advanced PID control is selected. (switch 203-1 = OFF)
2. Only when ON/OFF control is selected. (switch 203-1 = ON)
3. Invalid only for C200H-TV
03 (current output type).
4. Does not apply when Alarm Mode = 0.
5. Thermocouple = TC
Platinum Resistance Thermometer = Pt
4-2
Data Flow
Refer to
3-2 Data Flow
for the data flow in the Heat/Cool Temperature Control
Unit.
Data Settings
Before setting data with a user program or the Programming Console, turn ON
SW2-2 of the Unit to enable data setting from the C200H PC. However, the
executed bank number can be set with a user program or from the Programming
Console regardless of the ON/OFF setting of SW2-2.
SW2-1 (switching memory contents) may be set in either the OFF (Fixed) or ON
(Normal) position, but care is required as the setting of this switch changes the
stored data contents.
4-3
Programming
4-3-1 Example with SW2-1 in the Fixed Position
Description and Conditions
Example:
The user program makes the following settings:
Loop 1 SP = 80
°
C
Loop 2 SP = 200
°
C
Loop 1 executed bank number = 1
Loop 2 executed bank number = 3
Conditions: C200H-TV001 (thermocouple)
SW203 set to 2 (K).
Unit number set to 0 (allocated memory: IR100 to IR109).
SW2-1 set OFF (Fixed) and SW2-2 set ON (C200H PC).
Sample Program
MOV (21)
#0080
100
MOV (21)
#0200
101
MOV (21)
#1350
102
END (01)
10700
23515
10701
(C200H)
#1350 run bit ON
1 cycle ON
Fixed
Set #0080 for word 100 (Loop 1 SP).
Set #0200 for word 101 (Loop 2 SP).
Set #1350 for word 102 (executed bank number).
Loop 2 executed bank number
Loop 1 executed bank number
Loop 1, loop 2 begin operation
Programming
Section 4-3
46 / 71