9
C200H-TV10
ON
OFF
Setting
Input type
OFF
JPt 100
ON
Pt 100
The switch is factory-set to OFF.
See
Appendix B Sensor Temperature Measurement Range
for the measurable
temperature range.
Operation and Function Setting
SW203
Operation and Function Setting
13
4
5
6
2
OFF
ON
NO
Pin no.
Function
OFF
ON
6
Loop 1
Cooling control output
Pulses
Current output
5
SP write mode
Write to EEPROM
and RAM
Write to RAM only
4
Loop 2
Enabled
Disabled or not used
3
Display unit
°
C
°
F
2
Not used.
---
---
1
Control method
PID control
ON/OFF control
The switch is factory-set to OFF.
This setting is valid when the heating output type is “current,” and input loop 2 is
not used (i.e., when pin no. 4 of switch 203 is ON).
This setting selects the SP storage memory. Set it to ON if the writing is to be
frequently changed.
Loop 2
Set to “enabled” to use input loop 2, or to “disabled” to use only input loop 1. It is
not possible to use only input loop 2.
Note Always set this switch to the ON (disabled) position when input loop 2 is not
used. A sensor error occurs if this switch is set to the OFF (enabled) position
when no temperature sensor is connected to loop 2.
Display Unit
Selects whether displays and set values are shown on the Data Setting Console
in Celsius or in Fahrenheit.
Control Method
Selects the method of control.
Loop 1 Cooling Control
Output
SP Write Mode
Switch Settings
Section 2-2
14 / 71