Datasheet of C200H-DSC01 - DATA SETTING CONSOLE
Contact us: [email protected] Website: www.integrated-circuit.com
25
Display
level
Page
Default value
Data range
Bank
no.
Loop
no.
Read
Write
Display
symbol
Parameter
Dead band (see
note 1)
c-db
Yes
Yes
Yes
No
TC: –999 to
9999
°
C
Pt: –99.9 to
999.9
°
C
0
°
C
28
Cooling coeffi-
cient (see note 1)
c-sc
Yes
Yes
Yes
No
0.01 to 99.99
1.00
29
Heating control
period (see notes
1 and 3)
cp
Yes
Yes
Yes
No
1 to 99 s
20 s
29
Cooling control
period (see notes
1 and 3)
c-cp
Yes
Yes
Yes
No
1 to 99 s
20 s
29
Hysteresis (see
note 2)
hys
Yes
Yes
Yes
Yes
0.0
°
to 999.9
°
C
0.8
°
C
29
Alarm hysteresis
(see note 4)
hysa
Yes
Yes
Yes
No
0.0
°
to 999.9
°
C
0.2
°
C
30
Heater current
monitor (see
note 3)
ct
No
Yes
Yes
No
0.0 to 55.0 A
0.0 A
30
Heater burnout
current (see
note 3)
hb
Yes
Yes
Yes
No
0.0 to 50.0
0.0: No heater
burnout detec-
tion, alarm signal
OFF
50.0: No heater
burnout detec-
tion, alarm signal
ON
0.0 A
2
Heating output
variable monitor
h-o
No
Yes
Yes
No
0.0% to 100.0%
0.0 %
31
Cooling output
variable monitor
c-o
No
Yes
Yes
No
0.0% to 100.0%
0.0 %
31
Auto-tuning start/
stop (see note 1)
at
Yes
Yes
Yes
No
---
---
31
Copy bank
bcpy
Yes
Yes
Yes
No
---
---
31
Input-type monitor
in-t
No
Yes
No
No
0 to 9
Setting for
SW202
Alarm 1 mode
alt1
Yes
Yes
Yes
No
0 to 9
2
32
Alarm 2 mode
alt2
Yes
Yes
Yes
No
2
Yes:
Possible.
No:
Not possible or not required.
Note
1. Only when advanced PID control is selected. (switch 203-1 = OFF)
2. Only when ON/OFF control is selected. (switch 203-1 = ON)
3. Valid only for C200H-TV
03 (current output type).
4. Does not apply when Alarm Mode = 0.
5. Writing is not possible during operation (i.e., when RUN is ON).
6. Thermocouple = TC
Platinum Resistance Thermometer = Pt
Parameter Displays and Settings
Section 3-4
29 / 71