3-4-2 How to Display and Set Parameter Data
Basic Operation
When not specifically explained, use the keys as described in the following.
Changing the Display Level
When the Level Key is pressed, the leading parameter for each level is dis-
played.
Changing Parameters
When the Display Key is pressed, the parameters are displayed in order. There
may be skips depending on the model and DIP switch settings.
Changing the SV
Pressing the Up Key or the Down Key changes the SV. The SV is retrieved auto-
matically.
Changing the Loop
The loop is switched each time the Loop Key is pressed. It can be confirmed by
means of the LOOP 2 indicator.
PV and SV (Display Level 0)
PV
SV
Process temperature (monitored every 500 ms)
Set point of currently selected bank and loop (unit:
°
C or
°
F)
Valid SV Range
Set the set point in the range between the SV lower limit and the SV upper limit.
Error Display
When a sensor error occurs, one of the codes below and the detected tempera-
ture blink alternately in the PV display.
ser1
Temperature is out of the range: (sensor measurement range
+
10%FS). That is, 10%FS below the lower limit or 10%FS above
the upper limit Includes broken or incorrect sensor wiring
ser2
the upper limit. Includes broken or incorrect sensor wiring.
ser1
: Loop1 or Loop1 and Loop2 simultaneously.
ser2
: Loop2
serr
Abnormality in the cold junction compensating circuit. Applies to
thermocouple type only.
Bank Number (Display Level 0)
PV
SV
Bank number parameter symbol
Currently set bank number.
During control operation: Executed bank number
Control operation interrupted: Currently displayed bank number
Settings
•
The bank number can be changed.
•
The changed SV is reflected in the bank number display (BK).
Bank Number and Executed Bank Number
The executed bank number cannot be changed from the Data Setting Console.