Datasheet of C200H-DSC01 - DATA SETTING CONSOLE
Contact us: [email protected] Website: www.integrated-circuit.com
42
Parameter
Default value
Write/Read
data range
Actual data
range
Bank
no.
Loop
no.
Read
Write
Com-
mand
Alarm SV 1 (see note 4)
0
3
Yes
Yes
Yes
Yes
Alarm mode
TC 1, 4, 5:
0 to 9999
°
C
Other TCs:
–999 to
9999
°
C
0000 to
9999
F999 to
9999
0
°
C
Alarm SV 2 (see note 4)
0
4
Yes
Yes
Yes
Yes
9999
°
C
Pt 1, 4, 5:
0.0 to 999.9
°
C
Other Pts:
–99.9 to
999.9
°
C
0
°
C
Input shift value
0
5
Yes
Yes
Yes
Yes
–99.9 to
999.9
°
C
F999 to
9999
0.0
°
C
Proportional band (see
note 1)
0
6
Yes
Yes
Yes
Yes
0.0 to 999.9
°
C
0000 to
9999
40.0
°
C
Integral (reset) time
(see note 1)
0
7
Yes
Yes
Yes
Yes
0 to 9999 s
0000 to
9999
240 s
Derivative (rate) time
(see note 1)
0
8
Yes
Yes
Yes
Yes
0 to 9999 s
0000 to
9999
40 s
SP lower limit
1
0
Yes
Yes
Yes
No
Sensor measuring range
lower limit to (SP upper limit
value – 1 digit)
TC: –200
°
C
Pt: –99.9
°
C
SP upper limit
1
1
Yes
Yes
Yes
No
(SP lower limit + 1 digit) to
sensor measuring range up-
per limit
TC: 1,300
°
C
Pt: 450.0
°
C
Dead band (see note 1)
1
C
Yes
Yes
Yes
No
TC: –999 to 9999
°
C
Pt: –99.9 to 999.9
°
C
F999 to
9999
0
°
C
Cooling coefficient (see
note 1)
1
D
Yes
Yes
Yes
No
0.01 to 99.99
0001 to
9999
1.00
Heating control period
(see notes 1 and 3)
1
7
Yes
Yes
Yes
No
1 to 99 s
0001 to
99
20 s
Cooling control period
(see notes 1 and 3)
1
6
Yes
Yes
Yes
No
1 to 99 s
0001 to
99
20 s
Hysteresis (see note 2)
1
8
Yes
Yes
Yes
Yes
0.0 to 999.9
°
C
0000 to
9999
0.8
°
C
Alarm hysteresis (see
note 4)
1
9
Yes
Yes
Yes
No
0.0 to 999.9
°
C
0000 to
9999
0.2
°
C
Heater current monitor
(see note 3)
1
A
No
Yes
Yes
No
0.0 to 55.0 A
0000 to
0550
0.0 A
Heater burnout current
(see note 3)
1
B
Yes
Yes
Yes
No
0.0 to 50.0 A
0000 to
0050
0.0 A
(
)
0.0: No heater burnout
detection, alarm signal OFF
50.0: No heater burnout
detection, alarm signal ON
Heating control output
variable monitor
2
0
No
Yes
Yes
No
0.0 to 100.0%
0000 to
1000
0.0%
Cooling control output
variable monitor
2
6
No
Yes
Yes
No
0.0 to 100.0%
0000 to
1000
0.0%
Auto-tuning start/stop
(see note 1)
2
1
Yes
No
Yes
No
---
Start = 0001
Stop = 0000
---
Copy bank
2
2
Yes
No
Yes
No
---
0001
---
Input-type monitor
2
3
No
Yes
No
No
0 to 9
0000 to
0009
Setting for
SW202
Memory Allocation
Section 4-1
45 / 71
45 / 71