31
Control Output Variable Monitor (Display Level 2)
PV
SV
Heating control output variable monitor parameter
symbol
Heating output variable of currently selected loop
(Unit: %). Monitored every 500 ms.
PV
SV
Cooling control output variable monitor parameter
symbol
Cooling output variable of currently selected loop
(Unit: %). Monitored every 500 ms.
The relationship between the control output variable and control period is de-
fined by the formula below:
Control output variable (%) = x 100
ON time
Control period
The control output variable during ON/OFF control (when SW203-1 on the rear
panel is ON) is ON = 100% and OFF = 0%.
Auto-tuning Start/Stop (Display Level 2)
PV
SV
AT start/stop parameter symbol
AT indicator blinks
Process temperature
Set point
•
The auto-tuning operation begins when the Up Key is pressed. The PV and SV
return to the respective present temperature and set point displays. While
auto-tuning is in progress the AT indicator blinks.
•
To interrupt, press the Level and Display Keys again to display
at
. When
at
appears, press the Up Key. When the interrupt is executed, the AT display dis-
appears and the process temperature is displayed.
•
When auto-tuning is completed, the AT indicator stops blinking and the P, I, and
D data is written to EEPROM.
Copy Bank (Display Level 2)
PV
SV
Execute bank copy
Bank being copied
Bank copy completed
Copy bank parameter symbol
•
When the Up Key is pressed, the data other than the set point is copied from
bank number 1 to banks 2 through 8.
•
Use this method to create data in banks 2 through 8 by slightly modifying the
data in bank number 1.
Input-type Monitor (Display Level 2)
PV
SV
Input-type monitor parameter symbol
Input type currently set with SW202 on the rear panel.
Thermocouple: Setting no.
Platinum resistance thermometer: 0: JPt (OFF), 1: Pt (ON)
Note Cannot be set.
Parameter Displays and Settings
Section 3-4
35 / 71
35 / 71