Omni30 User Manual
- 52 -
© Omniflex
UMC1620AR04
Holding/
Input
Register
No.
Coil/
Input
Status.
DIT No.
DESCRIPTION
Read/
Write
231
N/A
230
Setup System Operation
Bit 0: Pushbutton Edge/#Level:
1 – Edge, 0 – Level
Bit 1: Auto ACK on Startup:
1 – NO Auto ACK on Startup, 0 - Auto ACK on Startup
Bit 2: Inhibit Input operation:
1 – Close to Inhibit, 0 – Open to Inhibit
Note:
This setting only applies when SW1-8 is ON. This input can be set only through serial port
Bit 3: Repeat Output operation (these repeats can be read only through serial port):
1 – Repeat Input status, 0 – Repeat Alarm status
Bit 4: Repeat Sense operation (these repeats can be read only through serial port):
1 – Normally de-energised, 0 – Normally energised (fail safe)
Bit 5-15: Reserved
232
N/A
231
Setup Slow Timer
The slow timer counts in multiples of the fast timer. This is configurable to allow the most flexible use of timers.
Some examples are given below:
To count in seconds:
set to 10
To count in 10s of seconds:
set to 100
To count in 20s of seconds:
set to 200
233-250
N/A
232 – 249
Reserved