Omni30 User Manual
- 48 -
© Omniflex
UMC1620AR04
Holding/
Input
Register
No.
Coil/
Input
Status.
DIT No.
DESCRIPTION
Read/
Write
Bits 4-15: Reserved
105
N/A
104
Lamp Status: Lamp 2 (high byte) : Lamp 1 (low byte)
The current lamp status for a given lamp can be read or written to here. Status for two lamps is provided per
Modbus register, one lamp per byte. Status is as follows:
0 = OFF
8 = FAST FLASH
16 = SLOW FLASH
24 = INTERMITTENT FAST FLASH
56 = STEADY ON
R/W
106
N/A
105
Lamp Status: Lamp 4 (high byte) : Lamp 3 (low byte)
R/W
107
N/A
106
Lamp Status: Lamp 6 (high byte) : Lamp 5 (low byte)
R/W
108
N/A
107
Lamp Status: Lamp 8 (high byte) : Lamp 7 (low byte)
R/W
109
N/A
108
Not Used
R/W
110
N/A
109
Not Used
R/W
111
N/A
110
Not Used
R/W
112
N/A
111
Not Used
R/W
113-115
N/A
112 – 114
Reserved
116
N/A
115
Fault Status
If the unit discovers a fault it is reflected in this register.
The error codes are as follows:
NO fault found:
0
INPUT fault:
47
SPI fault:
63
EEPROM fault:
79
R
117-200
N/A
116 – 199
Reserved
201-250
200 – 249
SETUP DATA
201
N/A
200
Setup Sequence Number: Input 2 (high byte) : Input 1 (low byte)
Select Sequence number from Table 4-1. DIP switches must be set to Sequence 31 on SW1 for this register to
R/W