Omni30 User Manual
- 47 -
© Omniflex
UMC1620AR04
Holding/
Input
Register
No.
Coil/
Input
Status.
DIT No.
DESCRIPTION
Read/
Write
14
:
14
15
:
15
16
:
16
102
17-32
101
Common Service Input Status
If any bit below is 1 then the input is ON.
Bit 0: INH (Inhibit input – NOT used in Omni30)
Bit 1: TST (Lamp Test input)
Bit 2: ACK (Accept/Acknowledge input)
Bit 3: SIL (Silence input – NOT used in Omni30)
Bit 4: RES (Reset input)
Bit 5: FS (Flash Sync input - this bit is READ ONLY)
Bit 6: FO (First Out input - this bit is READ ONLY)
Bits 7-15: Reserved
NOTE:
The SIL, ACK and RES bits are automatically reset to 0 after 3 seconds when set by the Modbus
Master. All other bits must be reset by the Modbus Master.
When using Modbus Coil writes (Modbus Function 5) the coil mapping is as follows:
Coil Number
: Control Input
17
:
INH (Inhibit input – NOT used in Omni30)
18
:
TST (Lamp Test input)
19
:
ACK (Acknowledge input)
20
:
SIL (Silence input – NOT used in Omni30)
21
:
RES (Reset input)
22-32 :
Reserved
R/W
103
N/A
102
Alarm Status
1 bit for every input where “1” means the input is in alarm and “0” means the input is in the normal condition. Bit
0 (lsb) = alarm status of input 1.
R
104
N/A
103
Common Service Output Status
If any bit below is 1 then the output (Relay) is energised
Bit 0: – not used
Bit 1: – HORN output
Bit 2: – GP output
Bit 3: – not used
R