Omni30 User Manual
- 20 -
© Omniflex
UMC1620AR04
Table 4-1: The Sequence Switch Settings
SEQUENCE
SWITCHES
SW1
SW2
SEQ.
NO.
1 2 3 4
5
6
7
8
1
2
3
4
5
6
7
8
DESCRIPTION
ISA
DESIGNATION
T
TIME DELAY ON...
0
0 0 0 0
0
0
0
0
0
0
FACTORY TEST MODE
1
1 0 0 0
0
1
0
0
0
0
LAMP FOLLOWS INPUT
--
--
2
0 1 0 0
0
0
1
0
0
0
MOMENTARY (FLEETING) ALARM
M-1
INPUTS
3
1 1 0 0
0
1
1
0
0
0
MOMENTARY ALARM, MANUAL RESET
A-1-4
INPUTS
4
0 0 1 0
0
0
0
1
0
0
MOMENTARY ALARM, MANUAL RESET WITH RINGBACK
R-1-10
INPUTS
5
1 0 1 0
0
1
0
1
0
0
MULTIPLE GROUP, FIRST OUT MANUAL RESET
F2M-1
--
6
0 1 1 0
0
0
1
1
0
0
FIRST OUT, AUTO RESET, F.O. RESET INTERLOCK
F3A-1-3
--
7
1 1 1 0
0
1
1
1
0
0
SINGLE GROUP, 1st OUT, MANUAL RESET, 1st UP CONTINUOUS FLASH
--
--
8
0 0 0 1
0
0
0
0
1
0
1st OUT, MANUAL RESET WITH NO SUBSEQUENT ALARM STATE ACCEPT PUSHBUTTON
F1M-1
INPUTS
9
1 0 0 1
0
1
0
0
1
0
MOMENTARY (FLEETING) ALARM MANUAL RESET
--
HORN
10
0 1 0 1
0
0
1
0
1
0
MOMENTAR RY (FLEETING) ALARM MANUAL RESET
--
REFLASH
11
1 1 0 1
0
1
1
0
1
0
MOMENTARY (FLEETING) ALARM MANUAL RESET FOR MOTOR ALARMS
--
INPUTS
12
0 0 1 1
0
0
0
1
1
0
MOMENTARY (FLEETING) ALARM
--
RETURN TO NORMAL
13
1 0 1 1
0
1
0
1
1
0
PULSE MONITORING ALARM WITH MANUAL RESET
--
--
14
1 0 0 0
1
1
0
0
0
1
MOMENTARY (FLEETING ALARM), MANUAL RESET, WITH RINGBACK.
18
0 1 0 0
1
0
1
0
0
1
MOMENTARY (FLEETING) ALARM AUTO RESET
--
INPUTS
21
1 0 1 0
1
1
0
1
0
1
MULTIPLE GROUP, FIRST OUT, AUTO RESET
F2A-1
--
23
1 1 1 0
1
1
1
1
0
1
SINGLE GROUP, 1st OUT, AUTO RESET, 1st UP CONTINUOUS FLASH
--
--
24
0 0 0 1
1
0
0
0
1
1
MULTIPLE GROUP, FIRST OUT, AUTO RESET, NO SUBSEQUENT ALARM STATE, ACCEPT PUSH BUTTON
F1A-1
--
25
1 0 0 1
1
1
0
0
1
1
MOMENTARY (FLEETING) ALARM AUTO RESET
--
HORN
26
0 1 0 1
1
0
1
0
1
1
MOMENTARY FLEETING ALARM, AUTO RESET
--
NO ACTION REALARM
27
1 1 0 1
1
1
1
0
1
1
MOMENTARY ALARM AUTO RESET FOR MOTOR ALARMS
--
INPUT
28
1 0 1 1
1
1
0
1
1
1
PULSE MONITORING ALARM AUTO RESET
--
--
31
1 1 1 1
1
1
1
1
0
1
0
0
1
0
0
1 SOFT-SET MODE. ALL SETTINGS ARE SET VIA SOFTWARE.
(Refer Table 4-2)
--
--
FOLLOWS INPUT
0
0
FOLLOWS ALARM
STATE
1
0
FUNCTION OF GROUP ALARM ON RELAY 3
NOTE:
ACTS AS RINGBACK
HORN
0
1
(G.A.)
In the above sequences, the switch
ACTS AS MRF
(REFLASH)
1
1
sense is as follows:
SW2=TIMERS/SEQUENCE 9-16
0
When SW1-8 is OFF, SW2 sets functions as shown in this table.
“1” = switch in on position
SW2=SERIAL PORT SETTINGS
1
#
#
#
#
#
#
#
#
When SW1-8 is ON , SW2 sets Serial Port Address and Baud Rate etc. See Section 4.7
“0” = switch in off position
CLOSE TO INHIBIT
0
With SW1-8 OFF, when SW2-6 is OFF, set Inhibit Input low to stop further alarms (serial port only)
OPEN TO INHIBIT
1
With SW1-8 ON, when SW2-6 is ON, set Inhibit Input high to stop further alarms (serial port only)
TIMERS OFF
0
With SW1-8 OFF and SW2-7 OFF: Timers are off, and SW2-1 to SW2-5 set the sequence of inputs 9-16
TIMERS ON
*
*
*
*
*
1
With SW1-8 OFF and SW2-7 ON: SW2-1 to SW2-5 sets Time-out value. See Figure 4-1
LAMP SENSE NORMAL
0
With SW1-8 OFF, when SW2-8 is OFF: Lamp outputs operate normally
LAMP SENSE REVERSE
1
With SW1-8 OFF when SW2-8 is on: Lamp outputs operate in reverse sense. i.e. On instead of off and v.v.