Omni30 User Manual
- 19 -
UMC1620AR04
COMPARISON OF DIP SWITCH MODE VERSUS SOFTSET MODE
CONFIGURATION OPTIONS
CONFIGURATION OPTION
DIP SWITCH
SET MODE
SOFT-SET
MODE
Lamp Sense
Setup Lamp Sense
All Lamps Normal Sense or Lamps Reversed Sense.
Note:
This setting only applies when SW1-8 is ON.
Yes
Yes
System Operation
Bit 0: Pushbutton Edge/Level Detection Option:
Bit 1: Auto ACK on Startup Option: Turn off running light
sequence
Bit 2: Inhibit Input operation Option:N/A in Omni30
Note:
Only applies when SW1-8 is ON.
Bit 3: Repeat Output operation Option: Repeat Input status or
Repeat Alarm status (via serial port only)
Bit 4: Repeat Sense operation Option: Normally de-
energised, Normally energised (fail safe) (via serial port only)
Bit 5-15: Reserved
No
No
Yes
No
No
Yes
Yes
Yes
Yes
Yes
4.3 Selecting the alarm/display logic sequences
There are two fundamental variations to the switch settings chosen, dependent upon the
settings of SW1-8 and SW2-7
First decide upon the setting of these two switches before proceeding to select the other
switch settings.
These are shown in the following table:
SW1-8
SW2-7
SW1-1 to 5
SW2-1 to 5
SW2-6 to 8
A
Off
Off
Sets sequence for
inputs 1-4
Sets sequence for
inputs 5-8
Operate as per
Table 4-1
B
Off
On
Sets sequence for
inputs 1-8
Sets Timer value
for all input timers.
Operate as per
Table 4-1
C
On
-
Sets sequence for
inputs 1-8
Sets Serial Port
address and R/W
Sets Baud Rate
etc.
NOTES:
1. Settings A and B are compatible with the previous Omni16a and Omni16b products.
2. When SW1-8 and SW2-7 are set as per A or B in the table above, the serial port
address defaults to 2, and the communications settings default to ASCII 9600 baud.
3. When SW1-8 is ON as per C in the table above, then the following default settings
apply:
Inhibit Contact Sense – not used in Omni30.
Lamp sense is set to normal.