Attention:
• Power the lift’s electrical system using a line fitted with a main braker and without any other
junctions.
• The devices fitted to provide protection against short circuits must take into account the
features of the electrical equipment:
Warnings for the installation of electric cables between the control unit and lift:
the connection cable that powers the safety limits switches on the lift must:
• Be adequately protected against the mechanical actions it may be exposed to during
use.
• Be passed through the dedicated cable glands (8) and connected to the terminal board
(9) inside the electric panel, respecting the numbering of the cable.
The electric power cable should be
AWG 10 wire.
NOMINAL POWER
NOMINAL POWER
HP
10
10
VOLTAGE
VOLTAGE
V
220 - 240
440 - 480
No. of phases
No. of phases
3
3
FREQUENCY
FREQUENCY
Hz
60
60
NOMINAL CURRENT
NOMINAL CURRENT
A
28
14
PICKUP CURRENT
PICKUP CURRENT
A
168
84
FUSE (DELAYED)
A
35
25
FUSE (FAST)
A
50
35
THERMOMAGNET
A
50
32
PROTECTION
TABLE / CONTROL
UNIT WIRING
TERMINAL BOARD
8
9