CHARGER FAULTS
The charger control circuitry constantly monitors for several fault conditions. If a fault should occur, the charge in progress is
interrupted, and a fault message is displayed on the LCD. A list of the faults and their descriptions follow.
Displayed Fault
Description
Fault LED
Fault Clearing
No DC Current
Check DC Fuse
Occurs when the DC fuse opens or no DC
output current.
Call Service – Yes
Bar Graph - Flashes
Can be reset by
disconnecting the battery
from charger. Replace fuse
or trouble shoot.
Battery
Disconnected
While
Charging!
Occurs when a charging battery is
disconnected from the charger without first
stopping the charge cycle.
Battery Disconnect -
YES
Bar Graph – Steady On
Can be reset by connecting a
battery to the charger.
Time To Gassing
Limit Exceeded
Occurs when the time limit to gassing
voltage is exceeded.
Time Limit Exceeded -
YES
Bar Graph – Steady On
Can be reset by
disconnecting the battery
from the charger
Overall Charge
Time Limit
Exceeded
Occurs when the overall charge cycle time
limit is exceeded
Time Limit Exceeded -
YES
Bar Graph – Steady On
Can be reset by
disconnecting the battery
from the charger
Time After
Gassing Limit
Exceeded
Occurs when the time limit after gassing is
exceeded
Time Limit Exceeded -
YES
Bar Graph – Steady On
Can be reset by
disconnecting the battery
from the charger
Low Battery
Voltage/ Check
Battery
Occurs when the battery is first connected
and the voltage is between 1.0 and 1.8
volts/cell*
Call Service – NO
Bar Graph – Steady On
Can be reset if battery
voltage is between 1.8 and
2.4 volts/cell
High Battery
Voltage/ Check
Battery
Occurs when the battery is first connected
and the voltage is above 2.4 volts/cell.
Call Service – NO
Bar Graph – Steady On
Can be reset if battery
voltage is between 1.8 and
2.4 volts/cell
Battery
Temperature/
Decreasing
Voltage
Occurs when there is negative change in
battery voltage
Call Service – NO
Bar Graph – Steady On
Can be reset by
disconnecting the battery
from the charger
High Amp-Hours
Occurs when more than 150% of battery
Amp-Hours are returned during the charge
cycle
Call Service – NO
Bar Graph – Steady On
Can be reset by
disconnecting battery from
the charger
AC Voltage Fault
Occurs when input AC voltage quality is
poor or distorted. Note that this condition
may be temporary. The charger will attempt
to re-start after 3 minutes. If unsuccessful,
will attempt a total of 4 times before a
permanent fault condition occurs.
Call Service – NO, ON
when fault is
permanent.
Bar Graph – Steady
ON, Flashes when fault
is permanent
Can be reset by
Disconnecting and
reconnecting battery to the
charger. Disconnect AC
power & check AC source.
AC fuse blown
Or lost phase
Occurs when AC fuse is blown or a phase of
AC power is interrupted when the charger is
charging a battery. Note that this condition
may be temporary. The charger will attempt
to re-start after 3 minutes. If unsuccessful,
will attempt a total of 4 times before a
permanent fault condition occurs.
Call Service – NO
Bar Graph – Steady
ON, Flashes when fault
is permanent
Can be reset by
Disconnecting and
reconnecting battery to the
charger. Disconnect AC
power & check AC source.
Summary of Contents for Millennium-E
Page 1: ...Owner s Manual ...
Page 8: ...The Ultimate Ice Resurfacer ...
Page 96: ...The Ultimate Ice Resurfacer 88 8 9 10 11 12 13 14 18 15 16 17 ...
Page 100: ...The Ultimate Ice Resurfacer 92 ...
Page 101: ...The Ultimate Ice Resurfacer 93 ...
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 115: ...I B 1561 Rev B Model ES3 EnForcer SCR Battery Charger Service Manual ...
Page 148: ...EnForcer SCR Service Manual I B 1561 34 ES3 REPLACEMENT PARTS SCHEMATICS ...
Page 156: ...EnForcer SCR Service Manual I B 1561 42 SCHEMATIC DIAGRAM ES3 ...
Page 157: ...EnForcer SCR Service Manual I B 1561 43 ES3 ASSEMBLY DRAWING ...
Page 159: ...EnForcer SCR Service Manual I B 1561 45 INTERIOR VIEWS ...
Page 160: ...EnForcer SCR Service Manual I B 1561 46 SINGLE EXTRUSION HEAT SINK ASSEMBLY ...
Page 162: ...EnForcer SCR Service Manual I B 1561 48 THREE EXTRUSION HEAT SINK ASSEMBLY ...
Page 164: ...EnForcer SCR Service Manual I B 1561 50 SUB ASSEMBLY PANEL ASSEMBLY ...
Page 167: ...EnForcer SCR Service Manual I B 1561 53 DOOR ASSEMBLY ...
Page 168: ...EnForcer SCR Service Manual I B 1561 54 PARALLEL CABLES OPTIONAL ...
Page 169: ...EnForcer SCR Service Manual I B 1561 55 DISCONNECT SWITCH OPTIONAL ...
Page 170: ...EnForcer SCR Service Manual I B 1561 56 CABINET ASSEMBLY ...
Page 171: ...EnForcer SCR Service Manual I B 1561 57 CABINET ASSEMBLY EXPLODED VIEW ...
Page 174: ...EnForcer SCR Service Manual I B 1561 60 SCHEMATIC DIAGRAM ...
Page 175: ...EnForcer SCR Service Manual I B 1561 62 ES3 LARGE CABINET ASSEMBLY DRAWINGS ...
Page 176: ...EnForcer SCR Service Manual I B 1561 63 CHARGER INTERIOR VIEW ...
Page 177: ...EnForcer SCR Service Manual I B 1561 64 TRANSFORMER CONNECTIONS ...
Page 178: ...EnForcer SCR Service Manual I B 1561 65 HEAT SINK ASSEMBLY ...
Page 179: ...EnForcer SCR Service Manual I B 1561 66 HEAT SINK ASSEMBLY CON T ...
Page 180: ...EnForcer SCR Service Manual I B 1561 67 SUB ASSEMBLY PANELS ...
Page 181: ...EnForcer SCR Service Manual I B 1561 68 CABINET ASSEMBLY ...
Page 182: ...EnForcer SCR Service Manual I B 1561 69 CABINET ASSEMBLY CON T ...
Page 183: ......
Page 184: ......
Page 185: ......
Page 186: ......
Page 187: ......
Page 188: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 197: ......