EnForcer™ SCR
Service Manual
I.B. 1561
23
Data Logging
While in Idle Mode or Done mode, hold down the
DOWN
and
UP
buttons (approximately 10 seconds) until the display reads
Data
Logging Selections.
Release the buttons and the display will read “
Number of Records:”.
Toggle the
EQUALIZE
button and the display will read
Display a Record?
The last record number will be shown at the bottom
right of the display.
Toggle the
DOWN
arrow keys to scroll through the available records. To view the contents of the individual record, toggle the
EQUALIZE
button. The Log Date will be displayed. To view the log data, toggle the
UP
or
DOWN
buttons. The log time, charge
parameters for that log can be read. To exit a particular log, press the
EQUALIZE
button. You can then continue to scroll through
different Data Logs with the
UP
and
DOWN
buttons. Select a new log again by pressing the
EQUALIZE
button. In order to exit
Data Logging at any time, press the
START/STOP
button.
The table below shows a list of the available Data Log parameters. The table shows the data in the order that it appears.
1. Log Date/Time
Date and time of log event
2. Log Store Code
1 = Daily charge Complete. 2 = Daily Charge Incomplete. 3 =
Equalize Charge Complete. 4 = Equalize Charge Incomplete.
3. Total Charge Cycles
Total Charge cycles greater than 1 hour
4. Total Equ. Cycles
Total Equalize cycles greater than 1 hour
5. Total Charge Amp-Hours/1000
Total Amp- Hours the charger has put out in thousands of Amp-
Hours.
6. Max. Charger Temperature *
Future option
7. Current Charger Temperature *
Future option
8. Minimum Charger Temperature *
Future option
9. Maximum Charger DC Volt
Max. DC volt for this particular charge cycle
10. Minimum Charger DC Volt
Min. DC volt for this particular charge cycle
11. BID Serial Number **
Future option
12. Battery Amp-Hour Rating
Battery Amp-hour setting from USER parameters
13. Battery Start Temperature *
Future option
14. Battery End Temperature *
Future option
15. Battery Cell Size
Battery Cell size from USER parameters
16. Equalize Count
Equalize count setting from USER Parameters
17. DC volts at Start
DC volts at beginning of charge cycle
18. DC volts at End
DC volts at end of charge cycle
19. Amp-Hours Returned
Amp hours returned for this particular charge cycle
20. DC Amps at Start
DC amps at beginning of charge cycle
21. DC Amps at End
DC amps at end of charge cycle
22. Pre 80% Charge Time
23. Total Charge Time
24. Charge Profile Used
Charge Profile 1-6 from Service Parameters.
25. Fault Code
1 = DC fuse, 2 = Open Battery, 3 = Time to gassing, 4 = Low
Battery, 5 = Overall Time Limit, 6 = Hot Battery, 7 = High Battery
Voltage, 8 = Time After Gassing, 9 = High Amp-Hours, 10 = AC
power distortion, 11 = AC fuse or single phase
*Note that all the temperature features are future features.
** Note the BID serial Number is a future feature
A total of 1000 events can be logged before data logger rolls over and overwrites previous data.
Summary of Contents for Millennium-E
Page 1: ...Owner s Manual ...
Page 8: ...The Ultimate Ice Resurfacer ...
Page 96: ...The Ultimate Ice Resurfacer 88 8 9 10 11 12 13 14 18 15 16 17 ...
Page 100: ...The Ultimate Ice Resurfacer 92 ...
Page 101: ...The Ultimate Ice Resurfacer 93 ...
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 115: ...I B 1561 Rev B Model ES3 EnForcer SCR Battery Charger Service Manual ...
Page 148: ...EnForcer SCR Service Manual I B 1561 34 ES3 REPLACEMENT PARTS SCHEMATICS ...
Page 156: ...EnForcer SCR Service Manual I B 1561 42 SCHEMATIC DIAGRAM ES3 ...
Page 157: ...EnForcer SCR Service Manual I B 1561 43 ES3 ASSEMBLY DRAWING ...
Page 159: ...EnForcer SCR Service Manual I B 1561 45 INTERIOR VIEWS ...
Page 160: ...EnForcer SCR Service Manual I B 1561 46 SINGLE EXTRUSION HEAT SINK ASSEMBLY ...
Page 162: ...EnForcer SCR Service Manual I B 1561 48 THREE EXTRUSION HEAT SINK ASSEMBLY ...
Page 164: ...EnForcer SCR Service Manual I B 1561 50 SUB ASSEMBLY PANEL ASSEMBLY ...
Page 167: ...EnForcer SCR Service Manual I B 1561 53 DOOR ASSEMBLY ...
Page 168: ...EnForcer SCR Service Manual I B 1561 54 PARALLEL CABLES OPTIONAL ...
Page 169: ...EnForcer SCR Service Manual I B 1561 55 DISCONNECT SWITCH OPTIONAL ...
Page 170: ...EnForcer SCR Service Manual I B 1561 56 CABINET ASSEMBLY ...
Page 171: ...EnForcer SCR Service Manual I B 1561 57 CABINET ASSEMBLY EXPLODED VIEW ...
Page 174: ...EnForcer SCR Service Manual I B 1561 60 SCHEMATIC DIAGRAM ...
Page 175: ...EnForcer SCR Service Manual I B 1561 62 ES3 LARGE CABINET ASSEMBLY DRAWINGS ...
Page 176: ...EnForcer SCR Service Manual I B 1561 63 CHARGER INTERIOR VIEW ...
Page 177: ...EnForcer SCR Service Manual I B 1561 64 TRANSFORMER CONNECTIONS ...
Page 178: ...EnForcer SCR Service Manual I B 1561 65 HEAT SINK ASSEMBLY ...
Page 179: ...EnForcer SCR Service Manual I B 1561 66 HEAT SINK ASSEMBLY CON T ...
Page 180: ...EnForcer SCR Service Manual I B 1561 67 SUB ASSEMBLY PANELS ...
Page 181: ...EnForcer SCR Service Manual I B 1561 68 CABINET ASSEMBLY ...
Page 182: ...EnForcer SCR Service Manual I B 1561 69 CABINET ASSEMBLY CON T ...
Page 183: ......
Page 184: ......
Page 185: ......
Page 186: ......
Page 187: ......
Page 188: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 197: ......