EnForcer™ SCR
Service Manual
I.B. 1561
14
If
Cool Down
is selected, at the end of charge the display will read:
Cool Down
In: 00:59
For the duration of the cool down period. After the cool down period has expired, the display will read “
Done/Battery
Available”
.
8. When the battery is disconnected, only the
POWER
LED remains lit and the display will return to “
Connect
Battery” / Time/ Date
alternately. The charge counter is incremented by one for the completed charge cycle.
USER PARAMETER CONFIGURATION
ENTER USER PARAMETERS
The charger’s User parameters may only be configured while the charger is in idle mode with no battery connected.
Press
Equalize
button and hold for approximately 5 seconds. The display will show: “
User Parameters”
. Release the
Equalize
button and the first User parameter: “
Set Clock/Calendar?”
is displayed.
ADJUSTING USER SETTINGS
:
Toggle the
UP
or
DOWN
arrow keys to scroll through the available User Parameters. To view the contents of the
variable displayed, toggle the Equalize button. The value of that setting will be displayed. To change the displayed
value, toggle the
UP
or
DOWN
arrow keys to the desired value. If you press and hold the
UP
or
DOWN
pushbuttons
for 3 seconds when adjusting the parameters, the options will scroll through at a rapid pace. Release the pushbutton
to return to normal scrolling mode. Once the desired value is chosen for that parameter, toggle the
Equalize
button
again to set it and to move on to the next parameter. In the case of setting the real time clock, toggle the
Equalize
button when “
Set Clock/Calendar?”
is displayed in order to enter the clock setting function.
Clock Minutes
is now
displayed. Choose the
Clock Minutes
by toggling the Equalize button again. To change
Clock Minutes
, scroll with
the
UP
or
DOWN
arrows. Press
Equalize
again to set the value. Scroll through the other real time clock value of
hours, days etc. by toggling the
UP
or
DOWN
arrow keys and set in a similar fashion. Press the
Start/Stop
key to
save and exit the real time clock function.
To exit and save from User Parameters
at any time, press the
Start/Stop
button. For a list of available user
parameters and their definitions, see the table below.
Parameters
Description
Range
Default
Battery
Selection
Select Battery 1-3
When
Battery Select
is enabled in
Service Parameters
, choose
between 1,2 or 3 completely different battery and charge profiles.
NOTE: This parameter is displayed when
Battery Select
is
enabled in Service Parameters.
1-3
1
Set
Clock/Calendar
Minute, Hours, Date etc.
Enter the set clock function to adjust the time/date.
This should be set to match current Date/Time
various
none
Battery Cell
Size
Battery Cell Size
Select the battery cell size to be charged. This value can be less
than or equal to the Charger nameplate cell size.
Do not adjust unless order acknowledgement specifies a change.
1-Charger
nameplate
cell size
18
Battery Amp-
Hours
Battery Amp Hour
Select the battery amp hour value. This value can be less than or
equal to the Charger nameplate amp hour value.
Do not adjust unless order acknowledgement specifies a change.
10 –
Charger
nameplate
amp hour
850
Summary of Contents for Millennium-E
Page 1: ...Owner s Manual ...
Page 8: ...The Ultimate Ice Resurfacer ...
Page 96: ...The Ultimate Ice Resurfacer 88 8 9 10 11 12 13 14 18 15 16 17 ...
Page 100: ...The Ultimate Ice Resurfacer 92 ...
Page 101: ...The Ultimate Ice Resurfacer 93 ...
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 115: ...I B 1561 Rev B Model ES3 EnForcer SCR Battery Charger Service Manual ...
Page 148: ...EnForcer SCR Service Manual I B 1561 34 ES3 REPLACEMENT PARTS SCHEMATICS ...
Page 156: ...EnForcer SCR Service Manual I B 1561 42 SCHEMATIC DIAGRAM ES3 ...
Page 157: ...EnForcer SCR Service Manual I B 1561 43 ES3 ASSEMBLY DRAWING ...
Page 159: ...EnForcer SCR Service Manual I B 1561 45 INTERIOR VIEWS ...
Page 160: ...EnForcer SCR Service Manual I B 1561 46 SINGLE EXTRUSION HEAT SINK ASSEMBLY ...
Page 162: ...EnForcer SCR Service Manual I B 1561 48 THREE EXTRUSION HEAT SINK ASSEMBLY ...
Page 164: ...EnForcer SCR Service Manual I B 1561 50 SUB ASSEMBLY PANEL ASSEMBLY ...
Page 167: ...EnForcer SCR Service Manual I B 1561 53 DOOR ASSEMBLY ...
Page 168: ...EnForcer SCR Service Manual I B 1561 54 PARALLEL CABLES OPTIONAL ...
Page 169: ...EnForcer SCR Service Manual I B 1561 55 DISCONNECT SWITCH OPTIONAL ...
Page 170: ...EnForcer SCR Service Manual I B 1561 56 CABINET ASSEMBLY ...
Page 171: ...EnForcer SCR Service Manual I B 1561 57 CABINET ASSEMBLY EXPLODED VIEW ...
Page 174: ...EnForcer SCR Service Manual I B 1561 60 SCHEMATIC DIAGRAM ...
Page 175: ...EnForcer SCR Service Manual I B 1561 62 ES3 LARGE CABINET ASSEMBLY DRAWINGS ...
Page 176: ...EnForcer SCR Service Manual I B 1561 63 CHARGER INTERIOR VIEW ...
Page 177: ...EnForcer SCR Service Manual I B 1561 64 TRANSFORMER CONNECTIONS ...
Page 178: ...EnForcer SCR Service Manual I B 1561 65 HEAT SINK ASSEMBLY ...
Page 179: ...EnForcer SCR Service Manual I B 1561 66 HEAT SINK ASSEMBLY CON T ...
Page 180: ...EnForcer SCR Service Manual I B 1561 67 SUB ASSEMBLY PANELS ...
Page 181: ...EnForcer SCR Service Manual I B 1561 68 CABINET ASSEMBLY ...
Page 182: ...EnForcer SCR Service Manual I B 1561 69 CABINET ASSEMBLY CON T ...
Page 183: ......
Page 184: ......
Page 185: ......
Page 186: ......
Page 187: ......
Page 188: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 197: ......