Date 29/6/2021
Document number 921100409_09_002
Page 53 of 73
53 / 73
choices are appeared NO/YES, if you select YES then by pressing
the SIREN SILENCE button the output will stop. By selecting NO the
output will stop only after a RESET.
- Pre-alarm: Same choices with the alarm menu.
- On a specific zone: Select task, delay (from NO up to 10 minutes)
and YES or NO at SIREN SILENCE.
- On task: Select task, delay (from NO up to 10 minutes) and YES or
NO at SIREN SILENCE.
Note: To program combinations you have to use the PC software.
5.3.7
AUX Relay
“
AUX RELAY
” option will open a step-by-step configuration to setup
the auxiliary relay. By default AUX relay is triggered by alarm. The
configuration steps are appearing with the following order:
-
Output mode (alarm/fault/prealarm/zone/task) *
-
Relay logic (positive/negative initial output position)
-
Delay (switching delay after triggering event)
-
Relay silence (select if the aux relay output will switch to initial
position after “SIREN SILENCE” command is given)
Figure5-24.Setup AUX relay
5.3.8
Extra Relays
“
EXTRA RELAYS
” option, similarly to AUX relay, will open a step-by-
step configuration to setup the extra relays. By default extra relays
are triggered by alarm. The configuration steps are appearing with
the following order:
-
Select extra relay (1 to 8)
-
Output mode (alarm/fault/prealarm/zone/task) *
-
Relay logic (positive/negative initial output position)
-
Delay (switching delay after triggering event)
-
Relay silence (select if this extra relay output will switch to
initial position after “SIREN SILENCE” command is given)
Figure5-25.Setup extra relays
*when a relay output (aux/extra) is set to FAULT event, after a fault
triggering event, only RESET will switch the relay back to normal
position. Combination of outputs is configurable only via the PC
software.