Date 29/6/2021
Document number 921100409_09_002
Page 72 of 73
72 / 73
Fuse type
Mains input: 4A/250V (Fast) TR5 – non replaceable
Battery: 900mA self resettable – non replaceable
Operating
temperature
range
-5 to 40 °C
Relative humidity
Up to 95% non-condensing
Construction
materials
ABS – polycarbonate / metal sheet with electrostatic paint
Dimensions
(LxWxH)
355 x 115 x 345 mm
Weight (without
batteries)
4,08kg
4,21kg
4,33kg
Manufactured in
accordance with
ΕΝ 54-2, ΕΝ 54-4
Warranty
2 years
Design
This device’s materials are selected according to the scope of use, meeting the
required specifications for operating environment conditions in compliance with
3K5 EN-60721-3-3: 1995.
9.1
Factory default settings
Registered points
None
Conventional sirens
All outputs enabled on general alarm, no delay
AUX relay
Enabled on general alarm, positive logic, no delay
(NO – C contacts active on alarm)
Extra relays
Enabled on general alarm, positive logic, no delay
Tasks
All deactivated
Enabled / disabled segments
All segments enabled (zones, points, sirens, etc.)
Working hours
05:00 until 23:00
Working days
Monday, Tuesday, Wednesday, Thursday, Friday
Panel address (panels network)
2
Buzzer
Enabled
Screen backlight
Power saving
Delays (general)
Enabled
Indication of points
Enabled
User code
1000
Technician code
1111
Max indicators per loop
10
Detector DAY alarm limit
100
Detector NIGHT alarm limit
100