![olympia electronics BSR-100 MAR Series Installation, Programming Operation, & Maintenance Manual Download Page 11](http://html1.mh-extra.com/html/olympia-electronics/bsr-100-mar-series/bsr-100-mar-series_installation-programming-operation-and-maintenance-manual_3865208011.webp)
Date 29/6/2021
Document number 921100409_09_002
Page 11 of 73
11 / 73
Figure 2-2.Prealarm on main screen
2.4
Alarm state
If a detection device triggers a fire alarm signal, the red "
GENERAL
ALARM
" indicator is being lit. On the
first row the message “
X – ALARMS
” is shown, where X represents the number of the current alarms.
Figure 2-3.Alarm on main screen
The second and the third row, describe the first and the last alarm event respectively. The name of the
point that triggered the alarm event, its zone and its loop & address are displayed.
Once the alarm state is activated, the built-in buzzer will play a long beeping sound and all outputs set to
operate in alarm mode will be activated. Pressing “
BUZZER SILENCE
” key will mute the buzzer until a
new event appears. Pressing “
SIREN SILENCE
” key will deactivate all sirens, as long as all other output
relays that are set to behave respectively under silence command.
To view all current alarms, press “
VIEW ALARMS
” key and navigate with up/down arrow.
2.5
Fault state
Similar to quiescent state, there is the fault state, when a fault appears. In fault state, the yellow
“
GENERAL FAULT
” indicator is lit, the built-in buzzer will sound and the fault relay will be triggered. In the
meanwhile, other LED indicators that refer to segments under fault may also be lit.
On the third row, additional information about the fault will appear, regarding its source. If there are more
faults, information about all the faults will be alternated.
Figure 2-4.Fault on main screen
Pressing “
BUZZER SILENCE
” will mute the buzzer until a new event appears
To view all current alarms, press “
VIEW ALARMS
” key and navigate with up/down arrow.