![Okofen PE 08 Operating Manual Download Page 56](http://html.mh-extra.com/html/okofen/pe-08/pe-08_operating-manual_730322056.webp)
56
Default values and settings
System Controlling
Settings
Boiler Temp Above
10.0°C
Boiler temperature
minimum
60.0°C
System Max
95.0°C
Boiler Pump On
Temp
60°C
Outside
Temperature – Time
of Average
4.0°C
Frost protection
Scavenging time
5 min
Frost protection
Pause Time
60 min
General
Language
Deutsch
(German)
USB
Recording
OFF
Recording interval
1 min
Sensor calibration
Sensor
all sensors 0.0°
C
Existing boiler
Valve switch on
temperature
60.0°C
Valve hysteresis
2.0°C
Inversion UV
NO
Delay time
30 min
Pump switch on
temperature
60.0°C
PE 567 EN 1.1