50
Default values and settings
Mode
ON
Temperature min
120 °C
Set Value ++
0 K
Limit above
30 %
Limit below
80 %
PID Controller - Amplify
4 %
PID Conttroller - Time Integral
Action
200 sec
PID Controller - Time Differential
Action
2 zs
Pellet level
Mode
Off
Threshold level
400 kg
Correction value
0 kg
Boiler Controlled Pump
On Temp
60 °C
Depends on Require
On
Pump type
Standard
Switch Off Hyst
3 K
Run On Time
15 min
Control range
5 K
Vacuum turbine
Filling
19:00
Tact RA Motor
55 sec
Pause RA Motor
5 sec
Suction intervall
180 min
Magnetventil
Mode
On
Min runtime
5 h
Washing time
60 sec
Settings
Control Temperature
70 °C
Switch Off Temp
76 °C
Malfunction mode
On / Off
Hand filling hopper
Off
Capacitive sensor RA -active
Off
Capacitive sensor ZW -active
Off
Switch on hyst
10 K
Output SM
Standard
Input AK
Standard
Outputs
PE 567 EN 1.1