144
ModBUS
113
3..116
6..4
4 M
Mo
od
dB
BU
US
S
Off
TCP Server
Defaultport for ModBUS is 502.
ModBUS Variables:
Variable
Register
Description
TEMP
2
Current cascade set temperature
TEMP_NEW
3
New cascade set temperature
TEMP_SET
4
If 1 the new cascade set temperature is adopted
FA_COUNT
5
Amount of boiler
PU_COUNT
6
Amount of accumulator
FEHLER CODE 1
10
First 4 digits errorcode, last digit user number (starts with 0)
e.g.: 50060 (sensor fracture boiler 0)
FEHLER CODE 2
11
FEHLER CODE 3
12
FEHLER CODE 4
1
FEHLER CODE 5
14
FA1_MODE
20
Boiler Mode 0=Off 1=Auto 2=On
FA1_MODE_NEW
21
New Mode
FA1_MODE_SET
22
If 1 the new mode is adopted
FA1_TEMP
23
Current boiler temperature
FA1_TEMP_NEW
24
New boiler temperature
PE 567 EN 1.1