106
System Regulation
13.13 System Regulation
In
Sys Regulation
you can input the parameters of the whole heating system.
If the Boiler temperature reaches the
Boiler Pump On Temp
, the pumps are given
free.
Note:
The temperature should be at a minimum of 60°C (for avoiding condensate in
the boiler).
The control range of the mixer starts at this temperature and ends at the
boiler min
temp
plus
BT controll range
.
In case of a burner demand, at least that temperature is required as boiler setpoint
temperature.
Note:
The temperature should be at a minimum of 60°C (for avoiding condensate in
the boiler).
If the boiler or the Accumulator reservoir reaches the
system temp max
, all heating
circuit pumps are activated for transporting the heat energy out of the boiler.
This process ends, if the boiler temp falls under the
system temp max
minus
boiler
superelevation.
This function sets, for which periode the outside temperature should be measured.
0 = no message
If the outside temperature falls below the
Frost Protection – Protection Temp
the
heating circuits are scavenged periodically. Default is 4°C, adjustable from –20 to 4°
C.
Note:
The Frost Protection is additionally always active: i.e. If the temperature of the
Flow sensor
or the
AC upper sensor
is 8°C, the burner demand activated.
PE 567 EN 1.1
Summary of Contents for PE 08
Page 16: ...16 Wiring diagrams PE 567 EN 1 1 ...
Page 17: ...Wiring diagrams 17 Operating Manual PELLEMATIC PE S K B 10 56 ...
Page 18: ...18 Wiring diagrams PE 567 EN 1 1 ...
Page 76: ...76 Code Input Menu of Pelletronic Touch after entering the code PE 567 EN 1 1 ...
Page 110: ...110 Cascade settings Back to the menu Sys Regulation PE 567 EN 1 1 ...
Page 168: ......
Page 169: ......