982017-AIR-BASIC-Multitower-T201-EN01.docx
Page 38 of 60
8
Dealing with minor faults
Let only trained specialist personnel carry out adjustments and troubleshooting. Standard settings for the
controller are made by the contractor during commissioning. The operator / maintainer is responsible for
any corrections and program adjustments! (See the following table)
Fault/display
Cause
Solution
Energy generator fault high pressure
(
Er 36
)
Energy transfer not ensured
Heating circuits excessively restricted
Open shut-off valves
one or more circulation pumps are not
pumping
Re-establish function
Speed (output level) of heating circulation
pump too low
Increase pump speed (stepper switch), delta
t = 5 K flow/return
Air in heating circuit
Vent heating circuit
3-way switching valve faulty
replace
Non-return valve stays shut
loosen, replace
with optional external DHW heating:
- Heat exchanger too small
- Heat exchanger scaled up or silted up
increase
Notify heating contractor, clean, descale
Controller set too high
Correct switch-off point downwards, 55°C is
the highest temperature!!!!
Loose terminal connections
Establish firm terminal connections
Heating system is not hot, heat
pump is hot up to buffer tank/low
loss header
Energy transfer is interrupted or too low
Replace circulation pump, vent heating
circuit, open gate valve, open control valves,
increase output level of DHW circulation
pump
Heat pump is running,
heating output too low
Excessive heat demand
Reduce heat load
Source system overstretched
Reduce heat load
Heat pump is switched to boiler priority
Check controller setting for DHW
Building design specification (e.g. thermal
insulation of building)
Ensure building meets its design
specification
Heat pump only produces DHW but
does not heat or heats too late
DHW target temperature is too high
Reduce switch-off point
Controller is in summer mode
Set controller to heating mode
Heat exchanger for DHW too small
Increase size of heat exchanger
DHW heat exchanger scaled up
Notify heating contractor,
clean, descale heat exchanger
DHW temperature not reached or
no longer reached
Heat exchanger for DHW is too small
Increase size of heat exchanger
Heat exchanger is scaled up
Descale heat exchanger
Sensor positioned incorrectly
Position correctly
Pipework too small
Install larger pipes
Faulty DHW sensor
replace
DHW charging pump faulty
replace
DHW charging pump output level set too
low
Set higher output levels
3-way switching valve faulty
replace
Heat pump runs continually and
yields only low temperature; traces
of oil in the appliance
Refrigerant leak
Loose fittings, refrigerant line leaking
Switch off heat pump,
notify customer service
Power-off operating state
A PSU lockout time from the energy supplier
is active
insufficient flow rate (
Er 91
)
The minimum flow rate at the heat pump is
not being reached.
Buffer charging pump faulty, diverter valve
faulty, insufficient system pressure, flow
sensor faulty
Table 5:
Troubleshooting
NOTE
Summary of Contents for AIR BASIC 211 T201
Page 50: ...982017 AIR BASIC Multitower T201 EN01 docx Page 50 of 60 11 8 Declaration of conformity...
Page 51: ...982017 AIR BASIC Multitower T201 EN01 docx Page 51 of 60...
Page 52: ...982017 AIR BASIC Multitower T201 EN01 docx Page 52 of 60...
Page 53: ...982017 AIR BASIC Multitower T201 EN01 docx Page 53 of 60...
Page 54: ...982017 AIR BASIC Multitower T201 EN01 docx Page 54 of 60 11 9 ERP Data...
Page 55: ...982017 AIR BASIC Multitower T201 EN01 docx Page 55 of 60...
Page 57: ...982017 AIR BASIC Multitower T201 EN01 docx Page 57 of 60...
Page 58: ...982017 AIR BASIC Multitower T201 EN01 docx Page 58 of 60...
Page 59: ...982017 AIR BASIC Multitower T201 EN01 docx Page 59 of 60...