5.1 Outdoor unit connection
If the appliance, the refrigerant lines, the fixing
points and the wall conduits are not properly
installed, structure-borne sound may be
transmitted to the building.
→
Ensure the refrigerant lines are secured in a
way to minimise structure-borne sound. The
system installer carrying out the work is
responsible for this.
Fit damp-proof and diffusion-proof insulation to
the refrigerant lines!
Use refrigerant pipes for the refrigeration
connection of the outdoor unit. OCHSNER
recommends using the solder-crimp fittings
supplied. If these have not been supplied with the
product, customer service will provide them when
commissioning the system.
Figure 37:
View of solder-crimp fitting
The solder-crimp fittings provide a better seal
than crimps made on site.
Leak rate < 1 g/year
CAUTION
OCHSNER customer service will solder the crimp
fittings professionally during commissioning.
Tighten the screws with the following tightening
torques:
Tightening torques for
solder-crimp fittings
Pipe
Connection Torque
Liquid line
Ø1/4"~6 mm
7
/
16
UNF
20 Nm
Liquid line
Ø3/8"~10 mm
⅝ UNF
30 Nm
Hot gas line
ؽ" ~12 mm
¾ UNF
60 Nm
Hot gas line
Ø⅝" ~16 mm
⅞ UNF
70 Nm
Table 3:
Tightening torques of solder-crimp fitting
Refrigerant pipe laying work will be charged
separately.
Procedure when NOT using the supplied solder-
crimp fittings
Step 1 of 3:
Undo the nuts from connections A (hot gas line)
and B (liquid line) of the refrigerant lines.
CAUTION
Ensure that no contamination (e.g. metal swarf) or
moisture enters the copper pipes. Therefore, hold
the pipe openings downwards and close them.
A
B
NOTE
NOTE
Summary of Contents for AIR BASIC 211 T201
Page 50: ...982017 AIR BASIC Multitower T201 EN01 docx Page 50 of 60 11 8 Declaration of conformity...
Page 51: ...982017 AIR BASIC Multitower T201 EN01 docx Page 51 of 60...
Page 52: ...982017 AIR BASIC Multitower T201 EN01 docx Page 52 of 60...
Page 53: ...982017 AIR BASIC Multitower T201 EN01 docx Page 53 of 60...
Page 54: ...982017 AIR BASIC Multitower T201 EN01 docx Page 54 of 60 11 9 ERP Data...
Page 55: ...982017 AIR BASIC Multitower T201 EN01 docx Page 55 of 60...
Page 57: ...982017 AIR BASIC Multitower T201 EN01 docx Page 57 of 60...
Page 58: ...982017 AIR BASIC Multitower T201 EN01 docx Page 58 of 60...
Page 59: ...982017 AIR BASIC Multitower T201 EN01 docx Page 59 of 60...