Option Setup
NOTE:
The Options screen is password-protected by default. This screen
should only be accessed by qualified personnel. If you do not have the
password contact your Nordson representative.
Touch the
CONFIG
button on the Navigation screen (Figure 16). A keypad
appears. Enter the password and touch the
ENT
key. The Option Setup
screen appears.
Figure 24 Option Setup Screen
This screen allows you to control the ability to change settings on the setup
screens, enable the external interlock, or restore system defaults.
Touch a screen button to toggle change access ON or OFF for the following
screens and functions. The factory default setting for each is listed, along
with the page number for the instructions for setting each screen’s functions.
Function or Screen
Default
Page
Temp. Setpoint Adjustments, Auto screen
ON
Temp. Setpoint, Display, and Alarms
ON
PID Control
OFF
Manual Mode
OFF
Timer and Ramp Control
ON
Temperature Offset and Power Limits
ON
External Run Signal
IGNORED
External Interlock Fault Mode
OFF
NOTE:
The ALLOW FORCE OUTPUTS function and the PLC I/O Display
screen are reserved for Nordson service only.
Restore System Defaults
The default power up state is
KEEP CURRENT VALUES
. To restore all
settings to the factory defaults, touch the button to toggle it to
RESTORE
SYS DEFAULTS
−
NEXT POWERUP
, then cycle dryer power.