WARNING:
Install a locking breaker or disconnect in the electrical supply
line ahead of the dryer so that power to the dryer can be disconnected and
locked out when repairs are made. All electrical connections must be made
according to code, including a proper ground connection. Failure to
observe this warning could result in severe personal injury or death from
electrical shock.
See Figure 9. Line power is supplied to the system through a
3
/
4
-in.
(1.9-cm) conduit fitting in the lower left-hand corner of the dryer exit end.
NOTE:
Wire gauge must be copper and comply with local and national
electrical codes.
1. Route three #6 AWG (13.3 mm
2
) wires to the input terminal block (TBL)
on the input side of the line filter.
2. Route one #6 AWG (13.3 mm
2
) ground wire to the cabinet grounding
terminal (PE) located next to the input terminal block.
WARNING:
DANGER!
Line filter terminals remain live even with the dryer
main disconnect in the Off position.
L3
L2
L1
GND
Figure 9
Power and Ground Connections