
PRELIMINARY: 24-Sep-2021
Page 63
002536MAN-00
OPERATION TROUBLESHOOTING -
HEATING MODE
Fault
Possible Cause
Verification
Recommended Action
Outdoor tempera-
ture reading is
incorrect by a
large amount
Outdoor EEV is mechani-
cally faulty and causing
electromagnetic interfer-
ence
Verify EEV operation (EEV3 or
EEV4) - see
EEV Troubleshooting
section
Replace outdoor EEV if faulty.
Faulty outdoor tempera-
ture sensor or outdoor
MODBUS board
Outdoor EEV verified to be good, no
loose connections in indoor to out-
door control wiring
Replace outdoor temperature
sensor or outdoor MODBUS
board.
High or low suc-
tion or discharge
pressure
Faulty sensor
Compare pressure sensor reading
against a known reference such as a
new refrigeration manifold set.
Check wiring, replace sensor. If
problem persists, replace con-
trol board.
High discharge
pressure:
Stage 1 - R410a or
Stage 2 - R134a
Low indoor loop flow rate Verify that indoor delta T is 8-12°F
(4-7°C)
Increase flow rate if new instal-
lation, check for fouled heat ex-
changer if existing installation.
Outdoor unit’s EEV3 or
EEV4 stuck almost closed
or partially blocked by for-
eign object
Manually adjusting the outdoor EEV
does not affect the superheat or the
suction pressure. High superheat,
low suction pressure.
Go to EEV troubleshooting sec-
tion.
Filter-dryer plugged
Feel each end of the filter-dryer; they
should be the same temperature. If
there is a temperature difference then
it is plugged. Also causes low suc-
tion pressure.
Replace filter-dryer.
Unit is overcharged
High subcooling, low Indoor Loop
delta T.
Remove 1/2 lb of refrigerant at
a time and verify that the dis-
charge pressure reduces.
Low suction
pressure:
Stage 1 - R410a or
Stage 2 - R134a
Indoor OUT temperature
too cold (on startup or if
unit has been off for ex-
tended period)
Ensure Indoor OUT temperature is
above the low limit indicated in the
Model Specific Information
section.
Reduce flow temporarily until
Indoor Out temperature has
risen sufficiently.
Low or no outdoor unit
airflow
Visually check outdoor fan to see if it
is operating.
Go to Outdoor Fan Trouble-
shooting section.
TS1 or TS2 temperature
sensors not reading
properly
If the sensor is reading low it will
cause the superheat to appear high,
which causes the EEV to continually
close.
Verify EEV position is low com-
pared to normal. Check tem-
perature sensor, replace if nec-
essary.
Filter-dryer plugged
Feel each end of the filter-dryer; they
should be the same temperature. If
there is a temperature difference then
it is plugged. Also causes high dis-
charge pressure.
Replace filter-dryer.
Outdoor unit’s EEV3 or
EEV4 stuck almost closed
or partially blocked by for-
eign object
Manually adjusting the outdoor EEV
does not affect the superheat or the
suction pressure. High superheat
and high discharge pressure.
Go to EEV troubleshooting sec-
tion.
Low refrigerant charge
Superheat is high, outdoor EEV posi-
tion is high.
Locate the leak and repair it.
Spray Nine, a sniffer, and/or
dye are common methods of
locating a leak.
Summary of Contents for ATWC Series
Page 15: ...PRELIMINARY 24 Sep 2021 Page 15 002536MAN 00...
Page 16: ...PRELIMINARY 24 Sep 2021 Page 16 002536MAN 00...
Page 17: ...PRELIMINARY 24 Sep 2021 Page 17 002536MAN 00...
Page 18: ...PRELIMINARY 24 Sep 2021 Page 18 002536MAN 00...
Page 20: ...PRELIMINARY 24 Sep 2021 Page 20 002536MAN 00...
Page 21: ...PRELIMINARY 24 Sep 2021 Page 21 002536MAN 00...
Page 22: ...PRELIMINARY 24 Sep 2021 Page 22 002536MAN 00...
Page 23: ...PRELIMINARY 24 Sep 2021 Page 23 002536MAN 00...
Page 24: ...PRELIMINARY 24 Sep 2021 Page 24 002536MAN 00...
Page 25: ...PRELIMINARY 24 Sep 2021 Page 25 002536MAN 00...
Page 26: ...PRELIMINARY 24 Sep 2021 Page 26 002536MAN 00...
Page 27: ...PRELIMINARY 24 Sep 2021 Page 27 002536MAN 00...
Page 28: ...PRELIMINARY 24 Sep 2021 Page 28 002536MAN 00...
Page 31: ...PRELIMINARY 24 Sep 2021 Page 31 002536MAN 00...
Page 81: ...PRELIMINARY 24 Sep 2021 Page 81 002536MAN 00...
Page 82: ...PRELIMINARY 24 Sep 2021 Page 82 002536MAN 00...
Page 83: ...PRELIMINARY 24 Sep 2021 Page 83 002536MAN 00...
Page 84: ...PRELIMINARY 24 Sep 2021 Page 84 002536MAN 00...
Page 85: ...PRELIMINARY 24 Sep 2021 Page 85 002536MAN 00...
Page 86: ...PRELIMINARY 24 Sep 2021 Page 86 002536MAN 00...
Page 87: ...PRELIMINARY 24 Sep 2021 Page 87 002536MAN 00...
Page 88: ...PRELIMINARY 24 Sep 2021 Page 88 002536MAN 00...
Page 89: ...PRELIMINARY 24 Sep 2021 Page 89 002536MAN 00...
Page 90: ...PRELIMINARY 24 Sep 2021 Page 90 002536MAN 00...
Page 91: ...PRELIMINARY 24 Sep 2021 Page 91 002536MAN 00...
Page 92: ...PRELIMINARY 24 Sep 2021 Page 92 002536MAN 00 Dimensions ATWC 45 55...
Page 93: ...PRELIMINARY 24 Sep 2021 Page 93 002536MAN 00 Dimensions ATWC 45 55...
Page 94: ...PRELIMINARY 24 Sep 2021 Page 94 002536MAN 00 Dimensions ATWC 65...
Page 95: ...PRELIMINARY 24 Sep 2021 Page 95 002536MAN 00 Dimensions ATWC 65...
Page 96: ...PRELIMINARY 24 Sep 2021 Page 96 002536MAN 00 Dimensions ATWC 75 80 100...
Page 97: ...PRELIMINARY 24 Sep 2021 Page 97 002536MAN 00 Dimensions ATWC 75 80 100...