COMPRESSOR TROUBLESHOOTING
Fault
Possible Cause
Verification
Recommended Action
Compressor will
not start:
Stage 1 - R410a or
Stage 2 - R134a
Faulty control board.
No 24vac output on STAGE1 or
STAGE2 when compressor should
be operating.
Replace control board.
Faulty run capacitor.
(Single phase only)
Check value with capacitance meter.
Should match label on capacitor.
Compressor will hum while trying to
start and then trip its overload.
Replace if faulty.
Loose or faulty wiring.
Check all compressor wiring, includ-
ing inside compressor electrical box.
Fix any loose connections. Re-
place any damaged wires.
Faulty compressor
contactor.
Voltage on line side with contactor
held closed, but no voltage on one
or both terminals on the load side.
Points pitted or burned.
Or, 24VAC across coil but contactor
will not engage.
Replace contactor.
Thermal overload on
compressor tripped.
Ohmmeter shows reading when
placed across R and S terminals
and infinity between C & R or C & S.
A valid resistance reading is present
again after the compressor has
cooled down.
Proceed to Operation Trouble-
shooting to determine the cause
of the thermal overload trip.
Burned out motor
(open winding)
Remove wires from compressor.
Ohmmeter shows infinite resistance
between any two terminals. Note:
Be sure compressor overload has
had a chance to reset. If compressor
is hot this may take several hours.
Replace the compressor.
Burned out motor
(shorted windings)
Remove wires from compressor.
Resistance between any two termi-
nals is below the specified value.
Replace the compressor.
Motor shorted to ground.
Remove wires from compressor.
Check for infinite resistance be-
tween each terminal and ground.
If any terminal to ground is not
infinite replace the compressor.
Seized compressor due to
locked or damaged
mechanism.
Compressor attempts to start but
trips its internal overload after a few
seconds. (Run capacitor already
verified)
Attempt to “rock” compressor
free. If normal operation cannot
be established, replace
compressor.
Compressor starts
hard
Start capacitor faulty.
(Single phase only)
Check with capacitance meter.
Check for black residue around
blowout hole on top of capacitor.
Replace if faulty.
Remove black residue in electri-
cal box if any.
Potential relay faulty.
(Single phase only)
Replace with new one and verify
compressor starts properly.
Replace if faulty.
Compressor is “tight” due
to damaged mechanism
Compressor attempts to start but
trips its internal overload after a few
seconds. Run capacitor has been
verified already.
Attempt to “rock” compressor
free. If normal operation cannot
be established, replace com-
pressor.
Summary of Contents for ATWC Series
Page 15: ...PRELIMINARY 24 Sep 2021 Page 15 002536MAN 00...
Page 16: ...PRELIMINARY 24 Sep 2021 Page 16 002536MAN 00...
Page 17: ...PRELIMINARY 24 Sep 2021 Page 17 002536MAN 00...
Page 18: ...PRELIMINARY 24 Sep 2021 Page 18 002536MAN 00...
Page 20: ...PRELIMINARY 24 Sep 2021 Page 20 002536MAN 00...
Page 21: ...PRELIMINARY 24 Sep 2021 Page 21 002536MAN 00...
Page 22: ...PRELIMINARY 24 Sep 2021 Page 22 002536MAN 00...
Page 23: ...PRELIMINARY 24 Sep 2021 Page 23 002536MAN 00...
Page 24: ...PRELIMINARY 24 Sep 2021 Page 24 002536MAN 00...
Page 25: ...PRELIMINARY 24 Sep 2021 Page 25 002536MAN 00...
Page 26: ...PRELIMINARY 24 Sep 2021 Page 26 002536MAN 00...
Page 27: ...PRELIMINARY 24 Sep 2021 Page 27 002536MAN 00...
Page 28: ...PRELIMINARY 24 Sep 2021 Page 28 002536MAN 00...
Page 31: ...PRELIMINARY 24 Sep 2021 Page 31 002536MAN 00...
Page 81: ...PRELIMINARY 24 Sep 2021 Page 81 002536MAN 00...
Page 82: ...PRELIMINARY 24 Sep 2021 Page 82 002536MAN 00...
Page 83: ...PRELIMINARY 24 Sep 2021 Page 83 002536MAN 00...
Page 84: ...PRELIMINARY 24 Sep 2021 Page 84 002536MAN 00...
Page 85: ...PRELIMINARY 24 Sep 2021 Page 85 002536MAN 00...
Page 86: ...PRELIMINARY 24 Sep 2021 Page 86 002536MAN 00...
Page 87: ...PRELIMINARY 24 Sep 2021 Page 87 002536MAN 00...
Page 88: ...PRELIMINARY 24 Sep 2021 Page 88 002536MAN 00...
Page 89: ...PRELIMINARY 24 Sep 2021 Page 89 002536MAN 00...
Page 90: ...PRELIMINARY 24 Sep 2021 Page 90 002536MAN 00...
Page 91: ...PRELIMINARY 24 Sep 2021 Page 91 002536MAN 00...
Page 92: ...PRELIMINARY 24 Sep 2021 Page 92 002536MAN 00 Dimensions ATWC 45 55...
Page 93: ...PRELIMINARY 24 Sep 2021 Page 93 002536MAN 00 Dimensions ATWC 45 55...
Page 94: ...PRELIMINARY 24 Sep 2021 Page 94 002536MAN 00 Dimensions ATWC 65...
Page 95: ...PRELIMINARY 24 Sep 2021 Page 95 002536MAN 00 Dimensions ATWC 65...
Page 96: ...PRELIMINARY 24 Sep 2021 Page 96 002536MAN 00 Dimensions ATWC 75 80 100...
Page 97: ...PRELIMINARY 24 Sep 2021 Page 97 002536MAN 00 Dimensions ATWC 75 80 100...