PRELIMINARY: 24-Sep-2021
Page 34
002536MAN-00
Outdoor Reset
As mentioned earlier, lower heating setpoints will translate directly into a higher COP (efficiency).
When
Control Source HYD
is set to
Setpoints
, an optional Outdoor Reset control algorithm is available for heating mode, which
reduces the heating temperature setpoints at warmer outdoor temperatures as measured by the outdoor unit. To enable it, simply
click on the
Outdoor Reset
button at the top of the
Setpoint Control
window. The button will change to say Enabled, the indicator will
come on and the Outdoor Reset Table will appear.
The table is created by subtracting the value of the Outdoor Reset Factor from the original setpoints once for each table row .
The user-selected Hot Setpoints are located in the top row(<5°F), and the next row down equals the row above minus the Outdoor
Reset Factor. The table row in use based on current outdoor temperature is shown in red.
It can be seen that as outdoor temperature rises and heating load falls, the heating mode buffer tank temperature will be de-
creased and a higher seasonal efficiency will result.
Setpoint Control Method 2 - Indoor Loop (ICR)
Two
Tanks
It is possible to use all of the
Setpoint Control Method 1
settings, and operate two buffer tanks: one for heated water and one for
chilled water. The heat pump will switch over to cooling tank when it receives an external “
O
” signal, and this signal (along with
C/
GND
) will also energize a 3-way valve to divert flow to the cold tank (see
Piping
section).
However, it is suggested to use
Method 4
(External HTS/CTS with two tanks) for this purpose. This will require two external tank
temperature sensors, but has the benefit of both tank temperatures being constantly monitored and also has the added
Auto Maintain
option (maintaining both hot and cold tank setpoints without the requirement for an external “
O
” signal).
RED—Heating
BLUE—Cooling
Click to enable Outdoor
Reset, or use LCD
Actual Setpoint
is reduced by
Outdoor Reset
Row in use will be
RED
Outdoor Reset Factor
adjusts the tempera-
ture difference be-
tween table rows
Change units of
Setpoint Control only
Summary of Contents for ATWC Series
Page 15: ...PRELIMINARY 24 Sep 2021 Page 15 002536MAN 00...
Page 16: ...PRELIMINARY 24 Sep 2021 Page 16 002536MAN 00...
Page 17: ...PRELIMINARY 24 Sep 2021 Page 17 002536MAN 00...
Page 18: ...PRELIMINARY 24 Sep 2021 Page 18 002536MAN 00...
Page 20: ...PRELIMINARY 24 Sep 2021 Page 20 002536MAN 00...
Page 21: ...PRELIMINARY 24 Sep 2021 Page 21 002536MAN 00...
Page 22: ...PRELIMINARY 24 Sep 2021 Page 22 002536MAN 00...
Page 23: ...PRELIMINARY 24 Sep 2021 Page 23 002536MAN 00...
Page 24: ...PRELIMINARY 24 Sep 2021 Page 24 002536MAN 00...
Page 25: ...PRELIMINARY 24 Sep 2021 Page 25 002536MAN 00...
Page 26: ...PRELIMINARY 24 Sep 2021 Page 26 002536MAN 00...
Page 27: ...PRELIMINARY 24 Sep 2021 Page 27 002536MAN 00...
Page 28: ...PRELIMINARY 24 Sep 2021 Page 28 002536MAN 00...
Page 31: ...PRELIMINARY 24 Sep 2021 Page 31 002536MAN 00...
Page 81: ...PRELIMINARY 24 Sep 2021 Page 81 002536MAN 00...
Page 82: ...PRELIMINARY 24 Sep 2021 Page 82 002536MAN 00...
Page 83: ...PRELIMINARY 24 Sep 2021 Page 83 002536MAN 00...
Page 84: ...PRELIMINARY 24 Sep 2021 Page 84 002536MAN 00...
Page 85: ...PRELIMINARY 24 Sep 2021 Page 85 002536MAN 00...
Page 86: ...PRELIMINARY 24 Sep 2021 Page 86 002536MAN 00...
Page 87: ...PRELIMINARY 24 Sep 2021 Page 87 002536MAN 00...
Page 88: ...PRELIMINARY 24 Sep 2021 Page 88 002536MAN 00...
Page 89: ...PRELIMINARY 24 Sep 2021 Page 89 002536MAN 00...
Page 90: ...PRELIMINARY 24 Sep 2021 Page 90 002536MAN 00...
Page 91: ...PRELIMINARY 24 Sep 2021 Page 91 002536MAN 00...
Page 92: ...PRELIMINARY 24 Sep 2021 Page 92 002536MAN 00 Dimensions ATWC 45 55...
Page 93: ...PRELIMINARY 24 Sep 2021 Page 93 002536MAN 00 Dimensions ATWC 45 55...
Page 94: ...PRELIMINARY 24 Sep 2021 Page 94 002536MAN 00 Dimensions ATWC 65...
Page 95: ...PRELIMINARY 24 Sep 2021 Page 95 002536MAN 00 Dimensions ATWC 65...
Page 96: ...PRELIMINARY 24 Sep 2021 Page 96 002536MAN 00 Dimensions ATWC 75 80 100...
Page 97: ...PRELIMINARY 24 Sep 2021 Page 97 002536MAN 00 Dimensions ATWC 75 80 100...