Piping
Indoor Loop Water Lines
The connections for the Indoor Loop circuit are 1” or
1-1/4” brass FNPT. They are labelled as INDOOR IN and
INDOOR OUT. The ports are located on the left side of the
unit near the back.
Recommended buffer tank piping is shown in diagrams on
following pages. They show all of the recommended compo-
nents as well as where they should be placed. If other types of
components are used or connected differently, this is done at
user’s discretion with the caution that heat pump may or may
not work properly.
Note there is a separate set of piping diagrams for
DHW heating heat pumps with the double wall condenser
option.
NOTE:
It is recommended that the water lines between the
heat pump and the buffer tank be copper or other high tempera-
ture piping.
NOTE:
Care should be taken when routing the water lines to
ensure that adequate access to the heat pump is maintained so
as to not compromise ease of serviceability.
The minimum buffer tank size should follow the rule of 8
US gallons per ton of heat pump capacity. The following table
shows the minimum buffer tank size for each heat pump along
with the recommended size. The recommended size will mini-
mize the number of starts per hour and provide longer runtimes
for improved efficiency.
TABLE 12 - Buffer Tank Size
Heat Pump Size
Minimum Size
gal (L)
Recommended Size
gal (L)
45
24 (90)
50 (190)
55
32 (120)
70 (265)
75
48 (180)
70 (265)
100
70 (265)
100 (380)
If a tank size is not available, use the next size larger tank.
65
40 (150)
70 (265)
80
52 (200)
70 (265)
Number of Tanks
All dedicated DHW heat pumps (with the double wall con-
denser option) require one DHW holding tank, equivalent in
function to the single buffer tank systems discussed below.
All space heating/cooling heat pumps with single wall con-
denser require at least
one buffer tank
. If there is one buffer
tank, it will contain the heated or chilled water. The water in the
tank will be chilled when the “
O”
signal is activated. This buffer
tank may have electric elements for auxiliary heat, or an existing
boiler may be used. See piping diagrams on following pages.
If there is need for heating and cooling simultaneously or
in close proximity, or if need for a seasonal switchover is to be
avoided,
two buffer tanks
maybe installed. One will be always
be heated, and one will be always be chilled, controlled using
the on-board
Setpoint Control
routine. This routine has two op-
tions: the “
O
” signal from an external controller may be used to
tell the heat pump to switch to cooling mode and cool the cold
tank, or the “
Auto Maintain
” function may be used to automati-
cally maintain both the hot and cold tanks without external input.
See
Operation
section, and piping diagrams on following pages.
See the chapter
One or Two Buffer Tanks?
near the begin-
ning of this manual for a discussion of this topic.
Summary of Contents for ATWC Series
Page 15: ...PRELIMINARY 24 Sep 2021 Page 15 002536MAN 00...
Page 16: ...PRELIMINARY 24 Sep 2021 Page 16 002536MAN 00...
Page 17: ...PRELIMINARY 24 Sep 2021 Page 17 002536MAN 00...
Page 18: ...PRELIMINARY 24 Sep 2021 Page 18 002536MAN 00...
Page 20: ...PRELIMINARY 24 Sep 2021 Page 20 002536MAN 00...
Page 21: ...PRELIMINARY 24 Sep 2021 Page 21 002536MAN 00...
Page 22: ...PRELIMINARY 24 Sep 2021 Page 22 002536MAN 00...
Page 23: ...PRELIMINARY 24 Sep 2021 Page 23 002536MAN 00...
Page 24: ...PRELIMINARY 24 Sep 2021 Page 24 002536MAN 00...
Page 25: ...PRELIMINARY 24 Sep 2021 Page 25 002536MAN 00...
Page 26: ...PRELIMINARY 24 Sep 2021 Page 26 002536MAN 00...
Page 27: ...PRELIMINARY 24 Sep 2021 Page 27 002536MAN 00...
Page 28: ...PRELIMINARY 24 Sep 2021 Page 28 002536MAN 00...
Page 31: ...PRELIMINARY 24 Sep 2021 Page 31 002536MAN 00...
Page 81: ...PRELIMINARY 24 Sep 2021 Page 81 002536MAN 00...
Page 82: ...PRELIMINARY 24 Sep 2021 Page 82 002536MAN 00...
Page 83: ...PRELIMINARY 24 Sep 2021 Page 83 002536MAN 00...
Page 84: ...PRELIMINARY 24 Sep 2021 Page 84 002536MAN 00...
Page 85: ...PRELIMINARY 24 Sep 2021 Page 85 002536MAN 00...
Page 86: ...PRELIMINARY 24 Sep 2021 Page 86 002536MAN 00...
Page 87: ...PRELIMINARY 24 Sep 2021 Page 87 002536MAN 00...
Page 88: ...PRELIMINARY 24 Sep 2021 Page 88 002536MAN 00...
Page 89: ...PRELIMINARY 24 Sep 2021 Page 89 002536MAN 00...
Page 90: ...PRELIMINARY 24 Sep 2021 Page 90 002536MAN 00...
Page 91: ...PRELIMINARY 24 Sep 2021 Page 91 002536MAN 00...
Page 92: ...PRELIMINARY 24 Sep 2021 Page 92 002536MAN 00 Dimensions ATWC 45 55...
Page 93: ...PRELIMINARY 24 Sep 2021 Page 93 002536MAN 00 Dimensions ATWC 45 55...
Page 94: ...PRELIMINARY 24 Sep 2021 Page 94 002536MAN 00 Dimensions ATWC 65...
Page 95: ...PRELIMINARY 24 Sep 2021 Page 95 002536MAN 00 Dimensions ATWC 65...
Page 96: ...PRELIMINARY 24 Sep 2021 Page 96 002536MAN 00 Dimensions ATWC 75 80 100...
Page 97: ...PRELIMINARY 24 Sep 2021 Page 97 002536MAN 00 Dimensions ATWC 75 80 100...