PRELIMINARY: 24-Sep-2021
Page 41
002536MAN-00
View-->Alarms, Limits and Faults (FAULTS tab):
This tab shows hardware faults that could occur. If one of these faults occurs there may be a problem with the control board hard-
ware, with LCD Display and buttons, or with a sensor.
If a fault occurs, some things to try:
Turn the power to the heat pump off for 20 seconds and then back on again.
Use the menu item
Tools-->Reset to Factory Defaults
. If this clears the fault then the system configuration will have to be
set up again.
For LCD Display or Menu Button faults, turn off the power, disconnect and reconnect the cable between the LCD display board
and the control board, then turn the power back on again.
If the fault persists then there is most likely a hardware problem, and the sensor, control board, or LCD display board will
need to be replaced.
IMPORTANT NOTE:
If the Indoor OUT (I_OUT) probe is faulty or disconnected, neither hydronic heating nor the auxiliary will operate
if using Setpoint Control. They will continue to operate under Signals or BACnet control.
Greyed out do not apply.
Fault Indicators
Erase the com-
pressor statistics
(only for if a
compressor
should need to
be replaced).
View-->Stage Stats
:
The compressor information: number of starts, run hours and starts per hour.
View-->Set Stage 2 Delay
:
Sets the delay before stage 2 is
engaged on a stage 1 demand.
(“0” = no stage 2 engaged on a
stage 1 call)
View-->Defrost History
:
Same as clicking on HISTORY button in
Control Panel
window (see previous page).
NEEDS
UPDATE
Summary of Contents for ATWC Series
Page 15: ...PRELIMINARY 24 Sep 2021 Page 15 002536MAN 00...
Page 16: ...PRELIMINARY 24 Sep 2021 Page 16 002536MAN 00...
Page 17: ...PRELIMINARY 24 Sep 2021 Page 17 002536MAN 00...
Page 18: ...PRELIMINARY 24 Sep 2021 Page 18 002536MAN 00...
Page 20: ...PRELIMINARY 24 Sep 2021 Page 20 002536MAN 00...
Page 21: ...PRELIMINARY 24 Sep 2021 Page 21 002536MAN 00...
Page 22: ...PRELIMINARY 24 Sep 2021 Page 22 002536MAN 00...
Page 23: ...PRELIMINARY 24 Sep 2021 Page 23 002536MAN 00...
Page 24: ...PRELIMINARY 24 Sep 2021 Page 24 002536MAN 00...
Page 25: ...PRELIMINARY 24 Sep 2021 Page 25 002536MAN 00...
Page 26: ...PRELIMINARY 24 Sep 2021 Page 26 002536MAN 00...
Page 27: ...PRELIMINARY 24 Sep 2021 Page 27 002536MAN 00...
Page 28: ...PRELIMINARY 24 Sep 2021 Page 28 002536MAN 00...
Page 31: ...PRELIMINARY 24 Sep 2021 Page 31 002536MAN 00...
Page 81: ...PRELIMINARY 24 Sep 2021 Page 81 002536MAN 00...
Page 82: ...PRELIMINARY 24 Sep 2021 Page 82 002536MAN 00...
Page 83: ...PRELIMINARY 24 Sep 2021 Page 83 002536MAN 00...
Page 84: ...PRELIMINARY 24 Sep 2021 Page 84 002536MAN 00...
Page 85: ...PRELIMINARY 24 Sep 2021 Page 85 002536MAN 00...
Page 86: ...PRELIMINARY 24 Sep 2021 Page 86 002536MAN 00...
Page 87: ...PRELIMINARY 24 Sep 2021 Page 87 002536MAN 00...
Page 88: ...PRELIMINARY 24 Sep 2021 Page 88 002536MAN 00...
Page 89: ...PRELIMINARY 24 Sep 2021 Page 89 002536MAN 00...
Page 90: ...PRELIMINARY 24 Sep 2021 Page 90 002536MAN 00...
Page 91: ...PRELIMINARY 24 Sep 2021 Page 91 002536MAN 00...
Page 92: ...PRELIMINARY 24 Sep 2021 Page 92 002536MAN 00 Dimensions ATWC 45 55...
Page 93: ...PRELIMINARY 24 Sep 2021 Page 93 002536MAN 00 Dimensions ATWC 45 55...
Page 94: ...PRELIMINARY 24 Sep 2021 Page 94 002536MAN 00 Dimensions ATWC 65...
Page 95: ...PRELIMINARY 24 Sep 2021 Page 95 002536MAN 00 Dimensions ATWC 65...
Page 96: ...PRELIMINARY 24 Sep 2021 Page 96 002536MAN 00 Dimensions ATWC 75 80 100...
Page 97: ...PRELIMINARY 24 Sep 2021 Page 97 002536MAN 00 Dimensions ATWC 75 80 100...