Byte 0-3: Actual measured primary variable current level IEE 754
Test of command:
Send command 45: FF FF FF FF FF 82 9A 1A AD 18 8C 2
D 04 40 80 00 00 D2
Receive command 45: FF FF FF FF FF 86 9A 1A AD 18 8C 2D 06 09 00 40 80 00 00 DD :
response code is 09, device is not under correct current mode.
7.1.21 Command 46: Trim primary variable current DAC
gain
Command formate:
Trim primary variable AO gain,so the current current value is accurate set to its max value.
Before implementing this command, use command 40 to set current to accurate primary variable
AO max value. If device is not under fixed primary variable current mode or current has not been set
to accurate max value, need to return response code 9---not under correct current mode.
Request:
Byte 0-3: Externally measured primary variable current level IEEE754, units of mA
Response:
Byte 0-3: Actual measured primary variable current level IEE 754
Test of command:
Send command 46: FF FF FF FF FF 82 9A 1A AD 18 8C 2
E 04 40 80 00 00 D1
Receive command 46: FF FF FF FF FF 86 9A 1A AD 18 8C 2E 06 09 00 40 80 00 00 DE :
response code is 09, device is not under correct current mode.
8 Maintaining
8.1 How to change the transmitter’s direction
1) The transmitter can be reversed to any direction.
2) Before reverse the transmitter, please loose the nut (Part No.1) under the transmitter.
3) Reverse the transmitter to the direction required, then screw and tighten the fixing nut.
Please reference to picture 8.1
Picture 8.1 Change the transmitter’s direction