User’s Manual
Rev1.0
Date:15/07/2015 User’s Manual
29
/
47
Digital setting address is as below.
Chart 6.3 Address of digital setting
Register
Usage
Restriction of
modification
Nature
Date
type
2000~2001
D001 Max flow
-1e5~1e6
Read/Write
Float
2002~2003
D002 Min flow
-1e5~1e6
Read/Write
Float
2004~2005
D003 Max frequency output
0~1e6
Read/Write
Float
2006~2007
D004 Min frequency output
-1e5~1e6
Read/Write
Float
2008~2009
D005 Small signal cut off
0~1e6
Read/Write
Float
2014~2015
D008 K factor
0~1e6
Read/Write
Float
2016~2017
D009 Density setting
0~1e6
Read/Write
Float
2018~2019
D010 Pipe inner diameter
0~1e6
Read/Write
Float
2020~2021
D011 Max temperature
-1e5~1e6
Read/Write
Float
2022~2023
D012 Min temperature
-1e5~1e6
Read/Write
Float
2024~2025
D013 Max pressure
-1e5~1e6
Read/Write
Float
2026~2027
D014 Min pressure
-1e5~1e6
Read/Write
Float
2028~2029
D015 Ambient pressure
0~1e6
Read/Write
Float
2030~2031
D016 Temperature for standard
condition
-1e5~1e6
Read/Write
Float
2032~2033
D017 Equivalent of pulse output
0~1e6
Read/Write
Float
2034~2035
D018 Length of rectangle pipeline
0~1e6
Read/Write
Float
2036~2037
D019 Width of rectangle pipeline
0~1e6
Read/Write
Float
2058~2059
D030 Temperature for standard
condition
0~20
Read/Write
Float
2064~2065
D033 Reference flow rate
0~1e6
Read/Write
Float
The chart above indicates the register address, usage of the register, restriction of modification,
read/write nature and date type. The register above are all holding register, the supporting function
code is 03,04,06,16 function code.
6.2 Commends
Function code 03 and 04 are the codes supported for reading the registers. Function code 06 is for
writing one register. Function code 16 is for wrting multi registers. Function code 06 is only
supported for writing short date. Function code 16 is supported for writing both short date and float
date.