Chart 6.2 Address of code setting
Register
Usage
Range
Nature
Date
type
1000
Pre-heating time (warm up) C01
1~99
Read only Short
1001
Density compensation C02
0~2
Read/Write Short
1002
Method of pulse output
0~2
Read/Write Short
1004
Output C05
0~2
Read/Write Short
1005
Pulse output parameter
0~3
Read/Write Short
1006
Damping C07
1~16
Read/Write Short
1007
Instrument number C08
Hart(0~15)
MB(1~99)
Read
Short
1008
Baud rate C09
1~24
Read
Short
1009
Unit of time C10
0~2
Read/Write Short
1010
Mass unit C11
0~2
Read/Write Short
1011
Volume unit C12
0~6
Read/Write Short
1012
Pressure unit C13
0~11
Read/Write Short
1013
Temperature unit C14
0~2
Read/Write Short
1014
Right digits number for total flow C15
0~5
Read/Write Short
1030
Time of circle display C31
0~30
Read/Write Short
1031
First paratmeter displayed in circle display C32
1~5
Read/Write Short
1032
Second paratmeter displayed in circle display
C33
0~5
Read/Write Short
1033
Third paratmeter displayed in circle display
C34
0~5
Read/Write Short
1034
Fourth paratmeter displayed in circle display
C35
0~5
Read/Write Short
1035
fifth paratmeter displayed in circle display C36 0~5
Read/Write Short
1039
Sequence of float C40
1~4
Read/Write Short
1040
Shape of pipeline C41
0~1
Read/Write Short
1042
The array length of moist control C43
5~50
Read/Write Short
1048
Status C49
0~10
Read/Write Short
1049
Total flow reset to 0 C50
0~1
Read/Write Short
Users can use function code 04 and 06 to access to the address for code setting above.