User’s Manual
Rev1.0
Date:15/07/2015 User’s Manual
22
/
47
5.2 Setting list
Please check chart 5.1 and 5.2 for code and digital setting address list.
Chart 5.1 Code setting address
Code setting
address
Item
Code
Description of code
C01
Start up time
01~99
Set the start up time within 1~99 seconds
C02
Density type
00
Display standard volume flow rate
01
Density preset, display mass flow
02
Display actual flow rate
C03
Pulse output type
00
pulse output off
01
Frequency output
02
Pulse equivalent output
C06
Pulse output
parameter
00
Flow rate
01
Temperature
02
Pressure
03
Total flow
C07
Damping
01~16
1~16 seconds
C08
Instrument number
00~99
For Modbus
00~15
For HART communication
C09
Baud rate
1
1200 no parity 1 stop bit
2
1200 even parity 1 stop bit
3
2400 no parity 1 stop bit
4
2400 even parity 1 stop bit
5
4800 no parity 1 stop bit
6
4800 even parity 1 stop bit
7
9600 no parity 1 stop bit
8
9600 even parity 1 stop bit
9
19200 no parity 1 stop bit
10
19200 even parity 1 stop bit
11
1200 odd parity 1 stop bit
12
2400 odd parity 1 stop bit
13
4800 odd parity 1 stop bit
14
9600 odd parity 1 stop bit
15
19200 odd parity 1 stop bit
16
38400 no parity 1 stop bit
17
38400 even parity 1 stop bit
18
38400 odd parity 1 stop bit
19
57600 no parity 1 stop bit
20
57600 even parity 1 stop bit
21
57600 odd parity 1 stop bit
22
115200 no parity 1 stop bit
23
115200 even parity 1 stop bit
24
115200 odd parity 1 stop bit