PROGRAMMABLE CONTROL OPTIONS
Low Voltage Cutout Level:
FACTORY DEFAULT: 1 (1.75VPC cutoff; 2.15VPC reset, VPC = Volts Per Cell)
RANGE: 1-3
The low voltage cutoff feature will disable scrub and sweep functions when the battery becomes discharged. The cutoff and reset thresholds are
selectable from three options. These are Option 1 – 1.75VPC cutoff, 2.15VPC reset; Option 2 – 1.75VPC cutoff, 2.09VPC reset; Option 3 – 1.83VPC
cutoff, 2.09VPC reset. To select the desired cutoff level perform the following steps:
1
Turn
the
main power key switch
to the
off
position.
2
Press and hold the
side broom down/on and the scrub system off switches
.
3
While holding both switches turn the
main power key switch
to the
on
position.
4
Continue to hold both switches until all indicators except the side broom down/on and scrub off indicators turn off (approximately two
seconds).
5
Release both switches.
6
The status display will now show a number from 1 to 3. Pressing and releasing the
side broom down/on switch
will increase the displayed
value until 3 is reached. The next press will return to 1. If 1 is selected, the cutoff level will be 1.75VPC & the reset level will be 2.15VPC. If 2
is selected, the cutoff level will be 1.75VPC & the reset level will be 2.09VPC. If 3 is selected, the cutoff level will be 1.83VPC & the reset level
will be 2.09VPC.
7
To save the new setting, turn the
main power key switch
to the
off
position.
8
The new setting will be saved and will remain in effect until it is changed again.
Control Unit Sleep Delay Period:
FACTORY DEFAULT: 1 (10 minutes)
RANGE: 0 - 9
If the CR 1100/1200 is left in an idle state for a period determined by the sleep delay setting the control unit will automatically turn off any accessories.
This is to conserve battery power. The sleep period is adjustable from 10 to 90 minutes in 10 minute increments. It can also be turned off. To change
the sleep delay period perform the following steps:
1
Turn
the
main power key switch
to the
off
position.
2
Press and hold the
scrub system off
and the
hopper up switches.
3
While holding both switches turn the
main power key switch
to the
on
position.
4
Continue to hold both switches until all indicators except the scrub system off and the hopper up indicators turn off (approximately 2
seconds).
5
Release both switches. The status display will now indicate a number from 0 to 9 depending on the current sleep delay period.
6
Pressing and releasing the
hopper up switch
will now select the delay period. The level will increment from 0 to 9. 0 = off (sleep disabled), 1
= 10 minutes, 2 = 20 minutes, ... up to 9 = 90 minutes.
7
To save the new setting, turn the
main power key switch
to the
off
position.
8
The new setting will be saved and will remain in effect until it is changed again.
Squeegee Raise-In-Reverse Time Period Adjustment:
FACTORY DEFAULT: 3 (2.5 seconds)
RANGE: 1 - 9
When backing up with the recovery system active, the control unit will automatically raise the squeegee just enough to prevent dragging on the
fl
oor.
The time that the squeegee is raised is adjustable from 2 to 4 seconds in .25 second increments. To adjust the distance the squeegee is raised in
reverse, perform the following steps:
1
Turn
the
main power key switch
to the
off
position.
2
Press and hold the
scrub system off
and the
vacuum switches.
3
While holding both switches turn the
main power key switch
to the
on
position.
4
Continue to hold both switches until all indicators except the scrub system off and vacuum indicator turn off (approximately 2 seconds).
5
Release both switches. The status display will now indicate a number from 1 to 9 depending on the current time period.
6
Pressing and releasing the
vacuum switch
will now select the time period. The level will increment from 1 to 9. 1 = 2 second, 2 = 2.25 seconds,
3 = 2.5 seconds, ... up to 9 = 4.0 seconds.
7
To save the new setting, turn the
main power key switch
to the
off
position.
8
The new setting will be saved and will remain in effect until it is changed again.